
Description
2.5 RS485 interface
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
19
Default communication settings
In the as-delivered state, the following default values are set:
Table 2- 3
Default Modbus RTU communication settings
Setting
Default value
Address
126
Baud rate
19200
Data format
8N2
Response time
0 (automatic)
Delaying the response time
The response time of the PAC1020 may have to be delayed to enable its operation as a slave
device with devices from other manufacturers on the bus. The PAC1020 can automatically
calculate the response time to suit the baud rate. This automatic calculation is set at the
factory. The delay time is individually adjustable between 1 ms and 255 ms.
Polarization
Polarization of the RS485 data lines must be implemented at another point on the bus. The
PAC1020 does not contain polarization resistors.
Содержание 7KM1020-0BA01-1DA0
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 22: ......
Страница 44: ...Commissioning 5 6 Checking the displayed measured values PAC1020 42 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Страница 78: ......
Страница 93: ......
Страница 94: ......