Connection
4.3 Connection examples
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
31
Example connections
1.
3
-
phase measurement, 4 conductors, unbalanced load, without voltage transformer,
with 3 current transformers
Connection type 3P4W
*
The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-2
Connection type 3P4W, without voltage transformer, with 3 current transformers
2.
3-phase measurement, 4 conductors, unbalanced load, with voltage transformer, with
3 current transformers
Connection type 3P4W
*
The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-3
Connection type 3P4W, with voltage transformer, with three current transformers
Содержание 7KM1020-0BA01-1DA0
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 22: ......
Страница 44: ...Commissioning 5 6 Checking the displayed measured values PAC1020 42 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Страница 78: ......
Страница 93: ......
Страница 94: ......