Technical data
10
Device configuration
•
1 optically isolated digital input
•
1 optically isolated digital output
•
1 RS485 interface for connecting to a PC or network
Measurement
Only for connection to AC voltage systems.
Measurement
Measuring method
Voltage measurement
True RMS measurement (TRMS),
zero blind measurement, gapless
Current measurement
True RMS measurement (TRMS),
zero blind measurement, gapless
Measured value acquisition
•
Power
•
Frequency
•
Power factor
Zero blind measurement, gapless
Waveform
Sinusoidal or distorted
Frequency of the relative fundamental 50/60 Hz
Measured value acquisition mode
Automatic line frequency detection
Measuring inputs for voltage
Measuring inputs for voltage
Measurable voltage
Rated voltage
57.7 V/ 100 V … 230 V/ 400 V
Min. measuring voltage U
L-N
11.5 V
Max. measuring voltage U
L-L
280 V
Zero point suppression level
Voltage L-N
10 V
Voltage L-L
17 V
Measuring category
(acc. to IEC/UL 61010-2-030)
Category
CAT III
Impulse withstand voltage
≥
9.6 kV (1.2/50
μs)
Input resistance (L N)
1.5
MΩ
Max. power consumption per phase
150 mW
Max. voltage at measuring input
U
L-N
300 V
Содержание 7KM1020-0BA01-1DA0
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 22: ......
Страница 44: ...Commissioning 5 6 Checking the displayed measured values PAC1020 42 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Страница 78: ......
Страница 93: ......
Страница 94: ......