6
05.01
6.7 DC link options
6-189
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
I/R
PM
PM
Central module with 4.1 mF (width: 100 mm)
Central module with 20 mF (width: 300 mm)
100
Distributed module
P600
M600
Adapter terminals, Order No.
for module width 50 – 200
mm 6SN1161–1AA01–0BA0
for module width 300 mm
6SN1161–1AA01–0AA0
1)
+
–
Cable length,
max. 5 m
Note:
The distributed
capacitor modules
may only be
mounted and
installed vertically.
Danger
1) Notice!
Do not use for module widths 50 – 200 mm.
Danger of death because the contact safety is
endangered!
Fig. 6-20
Mounting location for the capacitor modules
Depending on the line infeed used, several capacitor modules can be con-
nected in parallel.
For the capacitor modules with 2.8 mF and 4.1 mF, the total charge limit of the
line infeed may not be exceeded (refer to Chapter 1.3).
The capacitor modules 2.8 mF and 4.1 mF (central/distributed) must be dimen-
sioned/selected corresponding to the engineering table 1-4 in Chapter C.1.1
taking into account the charge limits of the infeed.
The 20 mF capacitor modules do not have to be taken into account in the 1-4
engineering table. They must be selected as required taking into account the
maximum number from Table 6-19.
Table 6-19
Maximum number of 20 mF capacitor modules
Infeed unit
Maximum that can be connected
1)
UI 5 kW
1
UI 10 kW
I/R 16 kW
3
UI 28 kW
I/R 36 kW...120 kW
5
1) Valid if all of the monitoring modules used are connected to the AC line supply.
Capacitor modules
that can be
connected
6 Infeed Modules
02.12