2.7 Infeed modules
2-59
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
2.7.2
Internal cooling
Cooling clearance
min. 100 mm clearance
Do not cover e.g., with cable,
to ensure the appropriate cooling
Cooling clearance
min. 100 mm
clearance
Fig. 2-8
Power module with inserted control unit, internal cooling
Note
The power loss is dissipated in the cabinet and must therefore be taken into
account when engineering/dimensioning the cabinet cooling.
10.04