7.2 Voltage matching
7-206
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
The infeed can be directly connected to a TN line supply for 3–ph. 400 V AC,
3–ph. 415 V AC, 3–ph. 480 V AC
For other voltage levels, the infeed can be connected through an autotrans-
former.
Commutating
reactor
Line supply/transformer for the factory
L3
L2
L1
PEN
NE module
U1 V1 W1
Line supply/transformer for the factory
Autotransformer
L3
L2
L1
PEN
U1 V1 W1
NE module
Commutating
reactor
TN–C line supply direct connection schematic
TN–C line supply with autotransformer direct connection
schematic
PE
PE
N
Z
Z
Line filter
Line filter
N (5 conductor)
Fig. 7-3
TN–C line supply connection schematic
Symmetrical 4–conductor or 5–conductor three–phase line supply with
grounded neutral point with a protective and neutral conductor connector con-
nected at the neutral point which, depending on the line supply type, uses one
or several conductors.
For other line supply types
1)
the NE module must be connected through
an isolating transformer.
1)
Harmonized transformer types are described in Siemens Catalog NC 60.
Connection types
Example:
TN–C line supply
TN–C line supply
TN–S line supply
TN–C–S line
supply