4-115
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
4.4.2
Wiring
SINUMERIK 840D and the ANA module are supplied from the SIMODRIVE line
supply voltage or from the SIMODRIVE monitoring module via the equipment
bus. There must be at least one NE module in the equipment group when an
ANA module is used. No provision has been made for any other type of voltage
supply and failure to use the supply provided could damage the unit.
Notice
It is not permissible to operate an ANA module on its own with a SIMODRIVE
monitoring module!
Power is supplied to downstream electrical axes via the DC link busbars (40
mm
2
) of the carrier module.
One position encoder for each axis can be evaluated on the ANA module.
S
X101:
Axis 1
S
X102:
Axis 2
The measuring system must always be plugged into the connector of the asso-
ciated axis.
Table 4-19
Connectors X101, X102; 15–pin sub–D plug connector (two–tier)
Pin
X101
1)
X102
1)
Function
1
PENC0
PENC2
Encoder power supply
2
M
M
Encoder power supply ground
3
AP0
AP2
Incremental signal A
4
AN0
AN2
Inverse incremental signal A
5
BMIDAT0
BMIDAT2
Data signal EnDat interface
6
BP0
BP2
Incremental signal B
7
BN0
BN2
Inverse incremental signal B
8
XBMIDAT0
XBMIDAT2
Inverse EnDat interface data signal
9
PSENSE0
PSENSE2
Remote sense encoder power supply (P)
10
RP0
RP2
Incremental signal R
11
MSENSE0
MSENSE2
Remote sense encoder power supply (M)
12
RN0
RN2
Inverse incremental signal R
13
M
M
Ground (for internal shields)
14
BMICLK0
BMICLK2
EnDat interface clock signal
15
XBMICLK0
XBMICLK2
Inverse EnDat interface clock signal
1)
The permissible voltage range for the common mode component of the
individual encoder signals (AP. AN. BP, BP, RP, RP) is 1.5...3.5 V.
Line supply
connection
Measuring
systems
4 Control Units