Communication System Manual
3WN6 Circuit-Breakers
Copyright Siemens AG 1998. All rights reserved.
Version1.0 (05/98)
48
T-Nr. Designation
Message
address
Value range
Value range
Value range
1:x
Setting values/
Protection
parameters
Releases
N and P
Releases
H and J/K
Releases
D and E/F
Note: Settable values/functions are highlighted in grey. The incremental settings for these values are
given on the next page.
x =
61
"a" release setting
current I
r
782, 1, 0, 22, 0
40 - 100 % I
n
(A)
40 - 100 % I
n
(A)
0; 40 - 100 % I
n
(A)
64
Time-lag class T
c
(trip
class)
38) 39)
782, 4, 0, 0, 0
0; 20 - 300
(0.1 s)
0; 20 - 300
(0.1 s)
20 - 300
(0.1 s)
65
"z" release setting
current I
d
782, 5, 0, 22, 0
200 - 40000 A
50 % I
n
- 12 I
n
(A)
125 % I
r
-12 I
r
(A)
66
"z" release delay t
d
782, 6, 0, 4,
130
20; 80 - 400 ms
20; 80 - 400 ms
20; 80 - 400 ms
71
"g" release setting
current I
g
783, 1, 0, 22, 0
160 - 1200 A
20 % I
n
-1200 A
20 % I
n
- 60 % I
n
(A)
72
"g" release delay t
g
783, 2, 0, 4,
130
100 - 500 ms
100 - 500 ms
100 - 500 ms
Messages 71 and 72 are only available with releases E/F, J/K and P.
81
"N" release setting
current I
N
785, 1, 0, 22, 0 20 % - 100 % I
n
(A)
20 % - 100 % I
n
(A)
20 % - 100 % I
n
(A)
82
"n" release setting
current I
i
785, 2, 0, 22, 0
150 % I
n
-
50000/65000 A
40)
0; 150 % I
n
-12 I
n
0; 150 % I
n
-12 I
n
83
"g/N" release type I
g
/N
785, 3, 0, 0, 0
0 - 5
0 - 1
0 - 1
84
I
n, ext
External current
transformer
785, 4, 0, 22, 0
315 - 3200 A
Message 84 for P release only
85
Release time or
alarm t
x
41)
785, 5, 0, 4,
130
0; 1 - 15 s
0; 1 - 15 s
0; 1 - 15 s
93
Current phase imbalance 790, 3, 0, 24, 0
0; 50 %
(5 - 50 % with
Z=F05)
0; 50 %
0; 50 %
101
Voltage phase
imbalance
792, 1, 0, 24, 0
0; 5 - 50 %
102
Reversal of direction of
power flow
792, 2, 0, 9, 3
0; -2000 kW to
+2000 kW
42)
Messages 101 - 106 are only available
for releases
103
Overfrequency f>
792, 3, 0, 28, 0
0; 15 - 500 Hz
N and P in conjunction with
the communication module with
104
Underfrequency f<
792, 4, 0, 28, 0
0; 15 - 500 Hz
measuring functions (Z=F05).
105
Overvoltage U>
792, 5, 0, 21, 0
0; 100 - 1000 V
106
Undervoltage U<
792, 6, 0, 21, 0
0; 100 - 1000 V
107
Load shedding
792, 7, 0, 24, 0
0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)
38)
These time vaues are in the range 2 - 30 s. The transferred values (20 - 300) must therefore be multiplied by 0.1.
39)
The function is deactivated with setting value "0". This also applies to T-Nr. 1:93, 1:101 - 108.
40)
Size I (<= 1600 A): 50 kA; Size II (> 1600 A): 60 kA.
41)
t
x
is the time delay for the trip or warning signal for setting values with T-Nr. 1:93, 1:101 - 108. If t
x
= 0, the delay = 0 s. The setting values with
T-Nr. 1:93, 1:101 - 108 can also be deactivated by setting the value as a parameter. With Z=F05, these setting values can be parameterized
as either a trip or a warning, see T-Nr. 1:111, OS1:2.
42)
Supply from below: >0; Supply from above: <0.
108
Load input
792, 8, 0, 24, 0
0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)