IV374E Rev.03
Installation and user manual
Date of issue : 2016-09-06
Page 20 of 63 + FR
3.11.2 Parallel cable installation
Shielded and double insulated control cables available must be interconnected in a ring
configuration between UPS modules as shown below. The parallel control board is mounted on
each UPS module. The ring configuration ensures high reliability of the control.
3.12 LBS installation
LBS system contains LCD set, cable connections and UPS installation.
3.12.1 LCD setting
Set every UPS of the systems to be LBS Master or LBS Slave. For instance if the UPS
belongs to LBS master system, its LBS setting must be set to Master.
One UPS set LBS to Master
520KVA 23-05-2014
ID:01 08:00
◄
Setting
Record
Version
►
Parallel ID 01
Internal Module amount 05
Float Volt Revise
0.003
Parallel Amount
04
LBS Disable
520KVA 23-05-2014
ID:01 08:00
◄
Setting
Record
Version
►
On-Line
Command
On-Line
Command