background image

User's Manual

PRO-RT 2U
Series UPS

Para Systems, Inc.

1455 Lemay Dr.

Carrollton, TX 75007

Phone: 1-972-446-7363

Fax: 1-972-446-9011

Internet: minutemanups.com

UPS Sizing:  sizemyups.com

PN - 34000526 R2

Содержание PRO1000RT2U

Страница 1: ...User s Manual PRO RT 2U Series UPS Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000526 R2...

Страница 2: ...2 2 Controls and Indicators 8 3 Installation 11 4 Operation 18 5 Obtaining Service 22 6 Troubleshooting 23 7 Replacing the Battery 24 8 Specifications 28 9 Limited Product Warranty 30 A1 Declaration...

Страница 3: ...ettra de correctement installer le syst me pour atteindre son rendement maximum en toute s curit CAUTION Connect the UPS to a two pole three wire grounded utility power AC wall outlet The receptacle m...

Страница 4: ...test Once the UPS has passed its self test the UPS will be ready for normal operation When the UPS is in the AC mode Press and then release the On Off Test button during the audible alarm s first beep...

Страница 5: ...prior written permission of Para Systems Given that Para Systems will continuously improve and de velop the product changes may be made to the information in this Manual at any time without obligation...

Страница 6: ...layed and the UPS will sound a constant alarm to indicate that there is an Overload condition Battery Capacity Bar Graph Displays the amount of Battery Ca pacity available in the AC and Battery mode a...

Страница 7: ...tacles are electrically wired into two segments to support the Load Shedding Function Labeled Load 1 Load 2 7 TheAlways On Battery Backup output receptacles LabeledAlways On does not support the Load...

Страница 8: ...nstable due to the weight distribution 2 The Rackmount Configuration is complete See Connecting your Equipm ent CONNECTING THE BATTERIES QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNING...

Страница 9: ...CONFIGURATION The tower configuration allows the user to install the UPS in the up right position The tower brackets are provided with the UPS Use two or more people when installing the UPS the UPS i...

Страница 10: ...arge electrical device into the output receptacles of the UPS COAX PROTECTION CONNECTION OPTIONAL Connect a cable modem CATV converter DSS receiver or DVR to the coax connectors on the rear panel of t...

Страница 11: ...will blink During normal AC operation the UPS will quietly and confidently protect your system from power anomalies The UPS will charge the batteries with the UPS in the on or off position when the UP...

Страница 12: ...tests the battery s condition If the battery is weak bad or disconnected the Weak Bad Battery icon will illuminate and the Battery Capacity Bar Graph will turn off the LCD screen will display error c...

Страница 13: ...r the UPS Check the specifications Chapter 5 Obtaining Service IF THE UPS REQUIRES SERVICE 1 Use the Troubleshooting section to eliminate obvious causes 2 Verify there are no tripped circuit breakers...

Страница 14: ...battery system can present a risk of electrical shock These batteries produce sufficient current to burn wire or tools very rapidly produc ing molten metal Observe these precautions when replacing th...

Страница 15: ...G 2 FIG 3 7 Disconnect the battery connectors FIG 2 8 Remove the four retaining screws for the battery retaining bracket FIG 2 9 Remove the battery retaining bracket and set aside 10 Grasp the battery...

Страница 16: ...ery Life 3 to 5 years Environmental factors do affect battery life High temperatures poor utility power and frequent short duration discharges have a negative impact on battery life 8 hours to 90 capa...

Страница 17: ...FIT NESS FORAPARTICULAR PURPOSE Some states do not permit limitation of implied warranties therefore the aforesaid limitation s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL...

Страница 18: ...33 32 Notes Notes...

Отзывы: