Note
:
The BAT+ of the UPS connect poles is connected to the anode (+) of the
positive battery, the BAT-N is connected to the cathode (-) of the positive battery and
the anode of the negative battery, the BAT- is connected to the cathode of the
negative battery.
Factory setting of the long-run unit is battery quantity 40pcs, battery capacity
12V xxAh. When connecting 32/34/36/38 batteries, please re-set desired battery
quantity and its capacity after UPS starts at AC mode. Charger current could be
adjusted automatically according to battery capacity selected. All related settings can
be done through LCD panel or monitoring software.
CAUTION!
Ensure correct polarity battery string series connection. i.e. inter-tier and inter
block connections are from (+) to (-)terminals.
Don’t mix batteries with different capacity or different brands, or even mix up
new and old batteries, either.
WARNING!
Ensure correct polarity of string end connections to the Battery Circuit Switch
and from the Battery Circuit Switch to the UPS terminals i.e. (+) to (+) / (-) to (-) but
disconnect one or more battery cell links in each tier. Do not reconnect these links
and do not close the battery circuit switch unless authorized by the commissioning
engineer.