IV374E Rev.03
Installation and user manual
Date of issue : 2016-09-06
Page 47 of 63 + FR
50
Model set wrong
Model setting of the UPS is incorrect.
4.5 Options
SNMP card
CAUTION!
For network management configuration and use, refer to the separate user
manual - Network Management Card with Environmental Monitor - shipped with the
CARD
.
Network Management Card replacement
(internal SNMP)
◆
Loosen the 2 torque screws (on each side of the card).
◆
Carefully pull out the card. Reverse the procedure for re-installation
The slot called SNMP supports the MEGAtec protocol. We advise that NetAgent II-3 port is also
a tool to remotely monitor and manage any UPS system
NetAgent II-3Ports supports the Modem Dial-in(PPP) function to enable the remote control via
the internet when the network is unavailable .
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making NetAgent
II a versatile management tool. NetAgent II also supports multiple languages and is setup for
web-based auto language detection .
Relay card
The card is used for providing the interface for UPS peripheral monitoring. The contact signals
can reflect UPS running status. The card is connected to peripheral monitoring devices via DB9
female to facilitate the effective monitoring of the real-time status of UPS and timely feedback the
status to monitor when abnormal situation occurs (such as UJPS failure, mains interruption, UPS
bypass and ect.). It is installed in the intelligent slot of the UPS.
The relay card includes 6 output ports and one input port. Please refer to the following table for
detail.
The definition of the pins is defined as below: