IV374E Rev.03
Installation and user manual
Date of issue : 2016-09-06
Page 13 of 63 + FR
(9) Module input connector slot
3.4 UPS Module LCD control panel
LCD control panel introduction
(1) LED(from top to bottom:
“alarm”, “bypass mode”, “battery mode”, “mains mode”)
(2) LCD display
(3) scroll button
(4) Off button
(5) On button
3.5 Installation notes
Note: Consider for the convenience of operation and maintenance, the space in
front and back of the cabinet should be left at least 100cm and 80cm respectively when
installing the cabinet .
◆
Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity,
flammable gas and liquid, corrosive. To avoid from high room temperature, a system of room
extractor fans is recommended to be installed. Air filters are available at the front grills, to be
periodically mainteined if the UPS operates in a dusty environment.
◆
The environment temperature around UPS should keep in a range of 0°C
~
40°C. If the
environment temperature exceeds 40°C, the rated load capacity should be reduced by 12
%
per
5°C. The max temperature can't be higher than 50°C.
◆
If the UPS is postioned at low temperature, it might be in a condensing condition.The UPS
can't be installed unless the internal and external of the equipment is fully dry. Otherwise, there will
be in danger of electric shock.
◆
Batteries should be mounted in an environment where the temperature is within the required
specs. Temperature is a major factor in determining battery life and capacity. In a normal
installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away
from heat sources or main air ventilation area, etc.