PJC211/212/221/222

     

2.0.2 - 2013

Cooling Signal Output

Values:  Normal (default)/Inverted

Set to Normal when using a hydraulic cooling pump.

Should be set to Inverted when using an electrical cooling pump with 

a 10 2380A-12/24V relay box

SETUP cont.

Cooling Power Save

Values:  ON (default)/OFF

ON sets the Cooling Pump into power save mode,which means the 

Cooling Pump output is dropping to 0 volt when the oil pressure is be-

low 10 bar for more than 10 seconds (Cooling Pump are turned OFF).

Tank Monitor

Values:  ON (default)/OFF

ON is when you have a tank monitor, oil level and Oil temp sensor. 

OFF is when you do not have a tank monitor and the display will show 

0°C and no alarm for high temperature or low level will not be trans-

mitted on the S-link.

Instance

Values:  --(default)/PORT/STARBOARD

Setting the PHC024 tank controller instance. For a mono hull boat

the instance should be ”--“.  If you have an catamaran with two 

PHC024 controllers then the one in the port hull should be set as

“PORT” and the one in the starboard hull as “STARBOARD”. This 

way the two controllers are shown in the panel display as two 

different oil tanks to monitor.                          

Main Switch

Press the button below 

 to return to the previous menu.

Press the button below 

 to edit the selected parameter.

Parameter value will start to blink, use joystick to alter value. 

Press the button below 

 to save edited parameter to device

Press the button below 

 to cancel editing without saving.

Location

Values:  BOW/STERN/BOW-STB/STERN-STB

Set the location for selected device. Use BOW or STERN in a conven-

tional thruster system. In a system with two bow or stern thrusters 

(i.e a catamaran), use BOW or STERN for port thruster, BOW-STB or 

STERN-STB for starboard thruster 

Cooling Pump 

Values:  Always Running/Temp Controlled(default)

When the option “Temp Controlled” is selected, the cooling pump will 

start when oil temperature exceeds 50°C and stop when the oil tem-

perature goes below 40°C.

On systems with two oil tanks, this setting will apply to both tanks.

                              

Содержание S-link PJC-212

Страница 1: ...anual EN Made in Norway Sleipner Motor AS 2013 SLEIPNER MOTOR AS P O Box 519 N 1612 Fredrikstad Norway Tel 47 69 30 00 60 Fax 47 69 30 00 70 w w w s i d e p o w e r c o m sidepower sleipner no PJC211 212 221 222 S link Control Panel SIDE POWER Thruster Systems v 2 0 2 ...

Страница 2: ...er and through a designated and approved interface you are still required to also install an original Sidepower control panel to enable efficient troubleshooting if necessary DECLARATION OF CONFORMITY We Sleipner Motor AS P O Box 519 N 1612 Fredrikstad Norway declare that this product with accompanying standard remote control systems complies with the essential health and safety requirements accor...

Страница 3: ...for easy docking runs thrusters at selected power Dual joysticks PJC 212 222 only Back lit LCD display with instant feedback System status alarms Amount of thrust direction of thrust Interactive multi language menus CAN Bus communication with thrusters and accessories Plug play cables with compact connectors Diagnostics and system setup via panel Built in audible alarm buzzer Connector for externa...

Страница 4: ...stick for thruster Information display see fol lowing pages for details Press both ON buttons simultanously to activate control panel Press to change between day and night light Press and hold for 3 seconds to access menu system and choose items in menus Press to de activate control panel or cancel or go back in menu system or mute internal alarm buzzer Panel Layout PJC 211 Panel Layout PJC 212 Ho...

Страница 5: ... control joystick for bow thruster Speed control joystick for stern thruster Holding function for auto running of bow and stern thrusters together in the direction of the arrows at selected power Press for more and for less power 6 steps If any control unit are running the thruster in op posite direction to the hold function the hold function will be deactivated Information display see following p...

Страница 6: ...ern thruster setup Battery indicator will be shown here in a single DC electric stern thruster setup DISPLAY IN NORMAL USE BOW STERN BOW STB STERN STB Examples of display for different panel applications PJC211 221 DC Electric Bow thruster PJC221 Hydraulic Bow thruster PJC221 AC Electric Bow thruster PJC212 222 DC Electric Bow thruster DC Electric Stern Thruster PJC222 Hydraulic Bow thruster Hydra...

Страница 7: ...stick panel if the thruster is defined as a bow thruster Indicating amount of thrust set by other control units in the system i e additonal PJC panels 8700 Retract panel input via 8730 S link external switch interface S link remote con trol etc If two or more units is set to run the thruster in opposite direction this information will not be shown FIRST TIME SETUP After installation of a S link th...

Страница 8: ...system or temperature above 115o C 100o C for PPC800 FW V1 013 or older SR150000 FW V1 006 or older Red backlight in display and continous short beeps If one or more of the thrusters enters an alarm state Voltage below 8 Volts both 12 and 24 Volt sys tems or temperature above 130o C 110o C for PPC800 FW V1 013 or older SR150000FWV1 006orolder Continuous beeps and the HOLD function will be cancelle...

Страница 9: ... by the LCD display in red color All alarms will show in display when panel is turned OFF This requires the S link and other system devices has power Critical alarms are also trigging internal and external buzzer a long beep every 2 seconds The buzzer can be silenced by pushing the button below this will also silence all other panels in the system Critical alarms LOW OIL LEVEL HIGH OIL TEMPERATURE...

Страница 10: ...NU for 3 seconds to enter the menu sys tem Use the stern joystick to select SETUP Press button below the symbol to enter the SETUP menu Use the stern joystick to select SYSTEM DEVICES Press button below the symbol to enter the SYSTEM DEVICES menu Use the stern joystick to set the pin code one number at the time press button below the symbol to jump to next number and confirm The pin code is 9 9 9 ...

Страница 11: ...ow These symbols will show what function each corresponding button have in the selected menu entry Return to previous menu Select highlighted menu text Save edited parameter Edit highlighted parameter Cancel editing without saving This symbol indicates that the stern joystick is used to move between menu items parameters MAIN MENU ITEMS Move between main menu items with the stern joystick STABILIZ...

Страница 12: ...ve between PHC 024 parameters with the stern joystick Press the button below to return to the previous menu Press the button below to edit the selected parameter Parameter value will start to blink use joystick to alter value Press the button below to save edited parameter to device Press the button below to cancel editing without saving Bow Stern Direction Values Normal default Inverted Switches ...

Страница 13: ...tamaran with two PHC024 controllers then the one in the port hull should be set as PORT and the one in the starboard hull as STARBOARD This way the two controllers are shown in the panel display as two different oil tanks to monitor Main Switch Press the button below to return to the previous menu Press the button below to edit the selected parameter Parameter value will start to blink use joystic...

Страница 14: ...STB for starboard thruster SETUP cont Function Values SR V ON OFF SRP 80 100 SRVP 130 210 SEP 30 240 SRVP 80 100 SRH SRHP Setup the control unit behaviour SR V ON OFF Retract thruster without speed controller PPC800 PHC 024 SR61242 or SR150000 SEP 30 240 Tunnel speed thruster PPC800 without retract SRP 80 100 Retract SR61242 with PPC800 both devices needs to be set to SRP 80 100 SRVP 130 210 Retra...

Страница 15: ...below to save edited parameter to device Press the button below to cancel editing without saving Thrust Values 0 100 Default 75 Set the amount of thrust given by the remote control In a bow stern configuration try to balance the thrust so that the boat moves straight sideways when both thrusters are operated simultanously with input from the remote only Location Values BOW STERN BOW STB STERN STB ...

Страница 16: ...at the panel Press the button below to return to the previous menu PPC800 DC Speed Control SR150000 Control unit for SRV80 SRV100 SRV130 SRV170 SRV210 SRH SR61242 Control unit for SR80 SR100 Motor Temp Temperature measured at the electric motor brushes Not implemented in SR61242 Contr Temp Temperature measured inside the controller Not implemented in SR61242 Voltage Motor Voltage measured at the c...

Страница 17: ...ow to edit the selected parameter Parameter value will start to blink use joystick to alter value Press the button below to save the edited parameter Press the button below to cancel editing without saving BACKLIGHT LEVEL Values 1 5 Set level of panel backlight in daylight mode 1 is lowest inten sity 5 is the highest BACKLIGHT NIGHT COLOR Values GREEN BLUE RED WHITE Select color of backlight in ni...

Страница 18: ... 7 X X X Motor relay fault Turn off thruster battery main switch Thruster must be serviced by author ized personel power OFF resets alarm Critical Error 8 X PPC800 output fail PPC800 must be sendt for service Low Motor Cur rent 9 X Thruster uses no power Check thruster connections or motor dead Motor Contactor 10 X X No current on motor relay coil Check motor relay connections short circuit or rel...

Страница 19: ... X Hydraulic oil lewel is to low Fill more hydraulic oil to the hydraulic tank Warning Return Filter 24 X Return filter element requiered replacing Warning Pres sure Filter 25 X Pressure filter element requiered replacing Warning High Speed 26 X WARNING High Speed Stabilizer not active Stabilizer Fault 27 X Any Stabilizer alarm Se stabilizer panel for more info AC Motor Over temp 28 X Hydraulic AC...

Страница 20: ...ontroller PJC 212 Proportional joystick control panel Bow and stern Station 1 Automatic Main Switch 8977 12 8977 24 or Manual main switch w ANL fuse Automatic Main Switch 8977 12 8977 24 or Manual main switch w ANL fuse S link control system End terminator End terminator PJC 212 Observe PPC battery terminal polarity S link supply S link external switch interface and remote optional S link external...

Страница 21: ...21 PJC211 212 221 222 2 0 2 2013 Measurements ...

Страница 22: ...2 221 222 2 0 2 2013 Supply 12V 24V DC S link External alarm buzzer 12V 24V DC max 0 5A Internal fuse relay External alarm buzzer connection Rear side of panel Connections for optional external buzzer audible alarm ...

Страница 23: ... S link device Location Serial number ie Thruster AMS PPC800 etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure easier ...

Страница 24: ...nc Nagasaki Tel 81 95 840 7977 Fax 81 95 840 7978 www turtle marine com info turtle marine com Malta S D Yachts Ltd Cali Tel 356 21 339 908 Fax 356 21 332 259 www sdyachts com info sdyachts com New Zealand Advance Trident Ltd Auckland Tel 64 9 845 5347 Fax 64 9 415 5348 www advancetrident com service advancetrident com Norway Sleipner Motor AS Fredrikstad Tel 47 69 30 00 60 Fax 47 69 30 00 70 www ...

Отзывы: