Operating Instructions
Chapter
11
V200/V300
8012227/YT87/2016-03-29
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
55
Subject to change without notice
Technical specifications
Minimum
Typical
Maximum
Output signal switching devices
(OSSDs)
2 PNP semiconductors, short-circuit protected
,
cross-circuit monitored
Switching voltage HIGH
(active, U
rms
) at 250 mA
V
S
– 2.7 V
V
S
Switching voltage LOW
(inactive)
0 V
0 V
3.5 V
Source switching current
6 mA
250 mA
Leakage current
250 µA
Load inductance
2.2 H
Load capacity at 50 Ω
2.2 µF
Permissible line resistance
between device and load
2.5 Ω
Test pulse data
Test pulse width
230 µs
300 µs
Test frequency
120 ms
Response time
20 ms
Switch off time
100 ms
Power-up delay of the OSSDs
from red to green
30 ms
Contactors
Permissible dropout time
300 ms
Permissible pick-up time
300 ms
7)
Applies to the voltage range between U
V
and 0 V.
8)
Switching currents
′
500 mA are allowed briefly (
′
100 ms).
9)
In the case of a fault (0 V cable open circuit) the maximum leakage current flowing in the OSSD cable. The
downstream controller must detect this status as LOW. A safe PLC (Programmable Logic Controller) must be
able to identify this status.
10)
Make sure to limit the individual cable resistance to the downstream controller to this value to ensure that a
cross-circuit between the outputs is safely detected. (Also note EN 60
204 Electrical Machine Equipment,
Part 1: General Requirements.)
11)
When active, the outputs are tested cyclically (brief LOW). When selecting the downstream controllers, make
sure that the test pulses do not result in deactivation when using the above parameters.