Prerequisites
•
Configuration has been transferred to the device.
Approach
1.
Check the following points:
°
The blue areas are not monitored. Persons cannot stay in blue areas or are
protected from movement of the robot by other measures.
°
The display on the lower edge visualizes the switching behavior of the fields.
Green = Field free; Red = detection in field. The Stop Field switches inputs
CI0 and CI1. If available, the Reduced Field switches the inputs CI2 and CI3.
°
Access to the hazardous area is only possible through the Stop Field.
°
It is not possible to bypass the fields, e.g. by stepping over them. It is not
possible to stay in the hazardous area without being detected in the Stop
Field.
2.
Click on
Next
.
Figure 15: Check configuration
CONFIGURATION
6
8025720/1A9R/2020-12-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | nanoScan3 Tool - URCap