RN200 user manual 23
It shows in detail all the information about an inverter. In the upper part it is possible to select
the desired inverter: press
ACK/ENTER
, use ▲ and ▼ to select the inverter, confirm with
ACK/ENTER
.
If the communication is set in NON-BROADCAST mode, much of the following information is
read directly by the inverters. Otherwise, as far as possible, operator configurations are shown.
The information shown is:
The inverter manufacturer.
The inverter model.
Some specific inverter options.
The presence and status of the grid relay inside the inverter that connects the voltage
generated to the external terminals.
The active (W), reactive (var) and apparent (VA) powers supplied by the inverter.
The nominal powers of the inverter: active (W), apparent (VA), reactive quadrant 1
(var), reactive quadrant 4 (var).
The active (W) and reactive (var) power setpoints. They are displayed with dashes if
at that moment the inverter is not able to supply the required powers (i.e. it is producing
the maximum possible, which, based on the environmental conditions, is lower than
the expected setpoint). Therefore, the dashes indicate that no power limitation is
active on the inverter.
In this mode, the measurements and states acquired by the Can Bus PMCB, which connects
all the SICES controllers, are displayed in a complete way.
This page shows the list of the controllers recognized on the Can Bus PMCB. It is useful for
diagnostic purposes. For each controller, it shows its unique address.
The screen is organized into four bands, placed one above the other:
MC (mains controllers).
GC and DST (genset controllers).
BTB (bus tie breaker controllers).
RN (renewable sources controllers).
For each band, it shows the list of addresses of the relative controllers that communicate on
PMCB. Therefore, some bands can also be empty.
This page shows the significant data of each GC (genset controller) that communicates over
the PMCB can bus. It uses one display line for each GC. If there are more than 7 GC, it shows
them all, rotating them on the display every two seconds: press and hold the
ESC/SHIFT
button to stop the rotation on the current display. If some measures are not available, they are
displayed with dashes.
The page is hidden if there are no GC controllers.
The upper part contains the total information (sum of all GC controllers). It is shown only if
there are at least two GC controllers. It contains:
The total rated active power of the running generators (kW).
The total active power supplied by the generators (kW).