12    RN200 user manual

 

 

 

The parameter is protected with a password: to modify the parameter, first enter the 
required password in parameter "0000" (see later). 

To modify a parameter, press the 

ACK/ENTER

 button: the sq

uare brackets flash. Use the ▲ 

and ▼ buttons to change the value and press 

ACK/ENTER

 to confirm or 

ESC/SHIFT

 to cancel 

the change. 

To exit the programming menu, press the 

ESC/SHIFT

 button several times until you return to 

the main page (which displays the word PROGRAM in the centre). 

 

You can directly access the last programming page displayed. This is possible if, when leaving 
the programming, instead of going back up the menus to the exit, keep the 

ESC/SHIFT

 button 

pressed  for  about  2  seconds  (or  change  the  operating  mode  from  OFF/RESET  to  MAN  or 
AUTO) . 

 

Some  parameters  are  represented  with  alphanumeric  or  hexadecimal  strings.  In  this  case, 
when  the 

ACK/ENTER

  button  is  pressed,  in  addition  to  flashing  the  square  brackets  that 

enclose the value, the controller displays a cursor under the first character of the string. 

With the ◄ and ► buttons it is possible to move the cursor under the character to be modified. 
Subsequently, using the ▲ and ▼ buttons it is possible to modify the selected character. The 
operation is to be repeated for all the characters to be changed. 

Press 

ACK/ENTER

 to confirm or 

ESC/SHIFT

 to cancel the change. 

 

Changing the parameters can be limited by means of four different protection levels, listed in 
order of priority. 

 

SICES password. 

 

MANUFACTURER password. 

 

INSTALLER password. 

 

USER password. 

If a password is equal to 0, it is considered "unassigned". By default, all passwords are set at 
"0", except for the password for the SICES level. 

Each  level  of  protection  allows  you  to  view  a  subset of  the  controller’s  parameters.  It  also 
allows you to view the parameters associated with a lower protection level. For example, the 
INSTALLER can view and modify all the parameters of his own protection level, but also those 
associated with the USER level. Each level also allows you to change your password and the 
passwords of the lower levels. 

The  SICES  protection  level  also  allows  you  to  view  and  modify  some  critical  system 
configuration parameters. This password is not configurable, but is supplied together with the 
controller. 

If a password is lost, you can reconfigure it by logging in with the higher level password. 
In case of loss of the "manufacturer" password, contact support. 

To  modify  a  password-protected  parameter,  first  enter  the  required  password  in  parameter 
"

0000 - Access code

", found in the "

1.1.1 Authentication

" menu. To be able to access it, it 

is necessary to enter the various menus and submenus following the path “

PROGRAM 

 1 

SYSTEM 

 1.1 Security 

 1.1.1 Authentication

”. Use the 

ESC/SHIFT

 button to go back to 

the upper menu, the 

ACK/ENTER

 button to enter a submenu. 

Содержание RN200

Страница 1: ...File name EAAM072500EN docx Rev 00 Date 03 08 2020 ID Document EAAM72500 Product RN200...

Страница 2: ...status bar 9 6 5 Display modes 11 6 5 1 Programming P XX 11 6 5 2 PLC L XX 13 6 5 3 Status information S XX 14 6 5 4 Electrical measures M XX 19 6 5 5 Renewable sources R XX 21 6 5 6 Measurements from...

Страница 3: ...rogress or for clarifying or specifying procedures Maintenance of this device must be carried out by qualified personnel in compliance with current regulations in order to avoid damage to people or th...

Страница 4: ...CB circuit breaker connecting one generator to the common bars RNCB circuit breaker that connects a group of renewable sources to the common bars MGCB circuit breaker that connects the common bars to...

Страница 5: ...ual The controller is ready for manual use of renewable sources Press the START button to start the inverters Press the STOP button to stop the inverters Press the RNCB button to open close the RNCB c...

Страница 6: ...HIFT RIGHT to increase the contrast darken Pressed together with the button UP and DOWN Allows to change the brightness of the lamps Allows to change the parameters of 10 units at a time Horizontal na...

Страница 7: ...historical archives force the exit from the BUS OFF mode of the Can Bus etc RNCB In the OFF RESET and AUTO modes the button is disabled In MAN it is used to open and or close the RNCB circuit breaker...

Страница 8: ...mode is REMOTE START The controller is in another operating mode Indicates the presence of at least one alarm Indicates the presence of at least one warning There are no anomalies Indicates that at l...

Страница 9: ...resent but below the tolerance range Flashing 75 on the voltages on the common bars are present but above the tolerance range The RNCB circuit breaker is open The RNCB circuit breaker is closed Flashi...

Страница 10: ...eter P 0499 P 0499 0 blue background P 0499 1 black background P 0499 2 white background The colour of the messages depends on the background colour selected and the type of information displayed The...

Страница 11: ...o a page The title can be replaced with information relating to the status of the system You can do it in three ways By holding down the ESC SHIFT button The title will be shown again when you release...

Страница 12: ...10 RN200 user manual will be displayed for two seconds and then return to display the status message requested by the sequence...

Страница 13: ...SHIFT button the first line 1 is temporarily substituted with a status message Use the and buttons to select the programming mode press them until PROGRAM appears on the display Then press the ACK EN...

Страница 14: ...rm or ESC SHIFT to cancel the change Changing the parameters can be limited by means of four different protection levels listed in order of priority SICES password MANUFACTURER password INSTALLER pass...

Страница 15: ...such as The title and description of the PLC program The date of the last modification The firmware version of PLC compiler and editor The average and maximum execution time These times are automatica...

Страница 16: ...controller i e those inputs whose value is not acquired by the hardware but is determined by the PLC program This page shows the status of all numeric temporary variables AT_XXX available for the PLC...

Страница 17: ...he unique serial number of the controller ID The codes of the currently loaded software on the controller If the main software code is displayed in REVERSE it means that a new version has been downloa...

Страница 18: ...progress o Communication in progress The MAC address of the physical network interface The name under which the controller registered on the network if using DHCP The IP address assigned to the contro...

Страница 19: ...logical status of the input If the DIF 3202 DIF 3204 and DIF 3206 functions are used when the input is activated the controller forces the display of the relative page The page S 11 displays the statu...

Страница 20: ...actually associated with the functions If more than 8 functions are used for the analogue inputs the controller displays them all by rotating them 8 at a time every two seconds holding the ESC SHIFT...

Страница 21: ...various parts of the plant This page is automatically adapted to the real conditions of the system For example the mains and the MCB circuit breaker are automatically hidden if there are no MC200 con...

Страница 22: ...ABLE SOURCES or LOADS is shown at the bottom right in order to identify the real source This page shows the reactive kvar and apparent kVA powers on the single phases and total for single phase system...

Страница 23: ...configured the controller shows them all rotating them on the display every two seconds keep the ESC SHIFT button pressed to stop the rotation on the current display For each inverter it shows Its num...

Страница 24: ...e current display If some measures are not available they are displayed with dashes The upper part contains the total information sum of all inverters This information is always present even if the co...

Страница 25: ...ive on the inverter In this mode the measurements and states acquired by the Can Bus PMCB which connects all the SICES controllers are displayed in a complete way This page shows the list of the contr...

Страница 26: ...ntroller For each MC it shows Its address on PMCB 2 digits The imported or exported active power kW The imported or exported reactive power kvar This page shows the significant data of each RN renewab...

Страница 27: ...e ACK ENTER button to access it Using the and buttons you can scroll through the different records in the archive Each record is identified by a number and by the date and time of storage The number i...

Страница 28: ...arantees the best performance For the configuration of the communication ports and for selecting the type of inverter refer to the technical manual Before proceeding with any type of command both manu...

Страница 29: ...ad the controller must first be in AUTO You can switch to REMOTE START in these ways By configuring a digital input on the controller If this input is active the controller switches to REMOTE START wh...

Страница 30: ...they cannot be started if there is no voltage on the connection point mains or generators The operator can use the START and STOP buttons to control the manual start or stop of the inverters but only...

Страница 31: ...nerators and inverters and therefore generating a black out The concept of SPINNING RESERVE does this It is basically a power reserve that must be guaranteed by the generators they as a whole must be...

Страница 32: ...f value for these parameters should be the consequence of a long term observation of the production of renewable sources in the plant Only in this way is it possible to find the lowest possible value...

Страница 33: ...oller includes a clock calendar used mainly for the functions Weekly working time of the inverters Recording of events with date and time in historical archives The setting of the date time is possibl...

Страница 34: ......

Страница 35: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...