RN200 user manual 5
Button
Function
ACK/ENTER
When an alarm or a warning occurs, a first press of the button deactivates the
siren. A further press of the button recognizes the presence of anomalies and
automatically removes the warnings (if the operating conditions have returned
to normal). If kept pressed for 5 seconds, it performs a complete reset of the
anomalies (including alarms).
In the pages that display the board's analogue/digital inputs and outputs, it
allows you to switch the display between logical, physical or function-related
states.
Activates the alarms scrolling mode if they do not fit in the display.
While viewing the parameter menus or the historical archive, it allows to enter
a submenu.
While viewing the parameters, it allows to start and confirm a change
operation.
Pressed together with the button
ESC/SHIFT:
•
Allows you to "accept" any anomalies on the non-volatile memory at
power up.
•
Allows to perform a pending firmware update at power up.
•
According to the selected page, if pressed for at least 5 seconds it
allows you to reset the counters, reload the default values for the
parameters, delete the historical archives, force the exit from the BUS
OFF mode of the Can Bus etc.
RNCB
In the "
OFF/RESET
" and "
AUTO
" modes, the button is disabled.
In "
MAN
" it is used to open and/or close the
RNCB
circuit breaker.
When you want to open the circuit breaker, a single press first involves
transferring the loads from the renewable sources to the generators or to the
mains and then opening it; if you want to open RNCB immediately, press and
hold the button for 1 second.
START
In MAN mode it can be used to control the start-up of the inverters for the
renewable sources. Note: starting of the inverters is only possible if
RNCB
is
closed and the voltage on the common bars is present and within tolerance.
When the controller is turned on:
•
Holding it together with the
STOP
button allows access to special
functions.
STOP
In
MAN
mode it is used to stop the inverters for the renewable sources.
In
OFF/RESET
mode, it turns on all the lamps in order to check their
efficiency (in this phase, the controller also activates the outputs configured
with the DOF.3153 function, allowing you to also test the lamps on the
panel).
When the controller is turned on:
•
Allows to repeat the test of the non-volatile memory if there are
errors.
•
Ignores any pending firmware update.
•
Holding it together with the
START
button allows access to special
functions.