RN200 user manual 19
outputs, the controller displays them all by rotating them (8 at a time) every two seconds:
holding down the
ESC/SHIFT
key stops rotation.
The page
S.19
is displayed only if DANOUT modules have been configured. It shows the
percentage value currently associated with the four analogue outputs of each DANOUT
module (the real corresponding electrical measurement depends on the configuration made
within the DANOUT module). The values are displayed in REVERSE if the DANOUT module
is not communicating correctly.
In this mode, the measurements made by the controller on the electrical lines are fully
displayed. The different pages can be scrolled using the horizontal navigation buttons ◄ and
►.
Under some electrical measures, the controller also displays a bar showing graphically the
value measured compared to the rated power: on the bar are also one or more notches
representing the eventual thresholds. The colour with which the band is filled is green if the
measure is in tolerance, yellow if the measure is out of tolerance.
It shows the layout of the system in a single-line format, highlighting:
Renewable sources, generators, utilities, mains and any storage system.
The RNCB, GCB (cumulative), MGCB and MCB circuit breakers.
The power flows, displayed with arrows in the various parts of the plant.
The measurement of active and reactive power in the various parts of the plant.
This page is automatically adapted to the real conditions of the system. For example, the
mains and the MCB circuit breaker are automatically hidden if there are no MC200 controllers
connected via Can Bus PMCB.
This page displays the voltages, frequency and phase’s sequence of the renewable sources.
The information really displayed depends on the configuration:
Three-phase system (P.0119=3) with neutral connected to the controller (P.0129=1).
The controller displays the three L-L voltages, the frequency, the phases sequence
and the neutral-B- voltage. By pressing the
ACK/ENTER
button, the L-N voltages are
displayed instead of the L-L voltages (press
ACK/ENTER
again to return to the L-L)
Three-phase system (P.0119=3) without neutral (P.0129=0). The controller displays
the three L-
L voltages, the frequency, the phase’s sequence.
Single phase system (P.0119=1). The controller displays the L-N voltage, frequency
and neutral-B- voltage.
At the bottom right, an icon for the RENEWABLE SOURCES is shown, allowing you to
immediately detect which is the source of the shown measurements.
This page
displays the voltages, frequency and phase’s sequence of the common bars. The
information really displayed depends on the configuration:
Three-phase system (P.0101=3) with neutral connected to the controller (P.0128=1).
The controller displays the three L-L voltages, the frequency, the phases sequence
and the neutral-B- voltage. By pressing the
ACK/ENTER
button, the L-N voltages are
displayed instead of the L-L voltages (press
ACK/ENTER
again to return to the L-L)