18 RN200 user manual
The page
S.14
is displayed only if DITEL modules have been configured. It displays the status
of the digital outputs of the DITEL modules. If a DITEL module does not communicate
correctly, the controller displays dashes instead of the state of the outputs.
By pressing the
ACK/ENTER
button, the inputs can be shown in three different ways:
LOGICAL STATE
: the controller shows the logic level of the output (active or inactive)
used in the management of the operating sequence.
PHISICAL STATE
: the controller shows the electrical level (active or inactive, or high
or low) actually present on the output; it can be opposite to the corresponding logical
state. It is displayed in REVERSE.
BY FUNCTION
: the controller shows a list of the functions actually associated with
the digital outputs, displaying the logical status (1/0) relating to each function,
regardless of the output actually associated with the functions. If more than 8 functions
are used for the digital outputs, the controller displays them all by rotating them (8 at
a time) every two seconds: holding the
ESC/SHIFT
button stops rotation.
The page
S.15
displays the electrical value of the analogue inputs of the controllers
(connectors JU, JK and JJ), including the emergency stop (EM-S). By pressing the
ACK/ENTER
button you can view the inputs in two different ways:
PHISICAL STATE
: the measurement in VDC is displayed for each input.
PER FUNZIONE
: the controller shows a list of the functions actually associated with
the analogue inputs, displaying the relative value acquired in VDC, regardless of the
input actually associated with the functions. If more than 8 functions are used for the
analogue inputs, the controller displays them all by rotating them (8 at a time) every
two seconds: holding the
ESC/SHIFT
button stops rotation.
The page
S.16
is displayed only if DITHERM or DIGRIN modules have been configured. In
the left part it shows the type of module actually connected (DIGRIN, DITHERM or "DITEMP"
if the module does not communicate correctly). On the right side it shows the temperatures
acquired by the modules. They can be replaced by:
“------“: if the expansion module does not transmit the measurement.
“OPEN”: if the expansion module signals that the sensor is disconnected.
“+OVER”: if the module signals that the input signal is too high, a symptom of a fault.
“-OVER”: if the module signals that the input signal has a too low value, a symptom of
a fault.
The page
S.17
is displayed only if DIVIT modules have been configured. On the right side it
shows the measurements acquired by the modules (without any conversion). They can be
replaced by:
“------“: if the expansion module does not transmit the measurement.
“OPEN”: if the expansion module signals that the sensor is disconnected.
“+OVER”: if the module signals that the input signal is too high, a symptom of a fault.
“-OVER”: if the module signals that the input signal has a too low value, a symptom of
a fault.
The page
S.18
normally shows the percentage value currently associated with the two
analogue outputs of the controller. Pressing the
ACK/ENTER
button, the controller shows the
outputs by function: the controller shows a list of the functions actually associated with the
analogue outputs, displaying the analogue value for each function, regardless of the output
actually associated with the functions. If more than 8 functions are used for the analogue