7-2. Connecting Load Cables
WARNING : ELECTRIC SHOCK
Always turn all the breakers OFF, place the starter switch in the STOP
position and stop the engine before attaching / detaching the load cable to
the output terminal or receptacle
.
Close the output terminal cover before operating.
Do not insert a pin, needle or other metal object into the receptacle.
Do not touch the generator if the generator or casing becomes wet during
operation.
CAUTION : FIRE
Do not connect the generator output to indoor wiring.
< Note >
When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
If using the N terminal, be careful that the currents of each phase are uniformed.
If using three-phase output with a single-phase three-wire type output simultaneously, use in a
range of total current, not exceed from the maximum rated output (12kW).
If using three-phase output simultaneously with a single-phase three-wire type output, be careful
as it is possible for the outputs to mutually affect each other.
Use proper tools when connecting a load to sufficiently tighten the connection. Failure to
sufficiently tightening will result in cable burnout.
Terminal cover must remain closed during operation or breaker will trip.
(1) Three-Phase Output Terminal
For three-phase load:
Terminal voltage is 240 V.
For single-phase load:
Terminal voltage is 139 V.
Load
L1
L2
L3
N
GROUND
Load
Load
Load
L1
L2
L3
N
GROUND