5. Equipment
5-1. Three-phase and Single-phase simultaneous Output
This generator is capable of generating three-phase and single-phase three-wire output
simultaneously. (Three-phase output terminal and single-phase three-wire output terminal are
equipped individually.)
Neither switching operation of output nor switching operation of wiring is needed.
< Note >
Refer to section
“
7-2. Connecting Load Cables
” for Load Connections.
If using three-phase output simultaneously with a single-phase three-wire type output, use
in a range where the total current does not exceed the rated current.
5-2. Available Output Monitor
The available generated output for each output power source is displayed digitally. You can
use the display selector switch to change the display in the following order: three-phase,
single-phase three-wire U-W output, and single-phase three-wire U-N output, and single-phase
three-wire W-N output. Output of three-phase is always displayed when the engine is started.
< Note >
Consider the digitally displayed available output as an
approximate estimate. Be sure to thoroughly consider the
displayed value and the used load capacity when using a load
such as a motor with large starting capacity.
The displayed output capacity might not be correct values if
using a four-wire connection (single-phase using the N
terminal) for a three-phase output power source. Connect to a
single-phase/three-line type power source if using a single-
phase power source.
If “- -” is displayed for the available output, it means that usage
has exceeded the rated capacity. Immediately stop the equipment being used and reduce the
load capacity of the equipment.
5-3. Spill Containment
WARNING : INJURY
Do not open the check door when the starter switch is in the AUTO or START
position. It will cause injury by rotating parts such as cooling fans and fan belt.
Always turn the
starter switch to the STOP position and stop the engine, then
close and lock OPERATION PANEL DOOR before checking or maintaining
the engine or any equipment.
Three-Phase and Single-Phase Three-Wire Output Terminal
U
W
L1
L2
L3
N
GROUND
Display Selector Switch