Doc
#
E166703
E-30
E: Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
NOTE
: The System Log Record is 20 bytes, consisting of the Record Header (12
bytes) and Payload (8 bytes). The Timestamp (6 bytes) is in the header. Typically,
software will retrieve only the timestamp and payload, yielding a 14-byte record. The
table below shows all defined payloads.
Group
(Event
group)
Event
(Event
within
group)
Mod
(Event
modifier)
Channel
(1-3 for
COMs,
0 for FW)
Parm1
Parm2
Parm3
Parm4
Comments
0
Startup
0
0
0
FW version
Meter Run
Firmware
Startup
1
Log Activity
1
log#
1-3
0xFF
0xFF
0xFF
0xFF
Reset
2
log#
1-3
0xFF
0xFF
0xFF
0xFF
Log Retrieval
Begin
3
log#
0-3
0xFF
0xFF
0xFF
0xFF
Log Retrieval
End
2
Clock Activity
1
old year
1-3
old month, day, hour, minute, second
Clock Changed
2
0
0
0xFF
0xFF
0xFF
0xFF
Daylight Time
On
3
0
0
0xFF
0xFF
0xFF
0xFF
Daylight Time
Off
3
System Resets
1
0
0-3
0xFF
id mm#
0xFF
0xFF
Max & Min
Reset
2
0
0-3
0xFF
id e#
0xFF
0xFF
Energy Reset
3
slot#
0-3
0xFF
acc_typ
#
0xFF
0xFF
Reset Relay
Board
Accumulators
4
Settings
Activity
1
0
1-3
0xFF
0xFF
0xFF
0xFF
Password
Changed
2
0
1-3
old
V-Switch
new V-
Switch
0xFF
0xFF
V-Switch
Changed
Содержание MP200