Doc
#
E166703
2-15
2: MP200 Metering System Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Switching rate max.:
10/s
Mechanical life:
5 x 10
7
switching operations
Electrical life:
10
5
switching operations at rated
current
Breakdown voltage:
AC 1000 V between open contacts
Isolation:
AC 3000 V / 5000 V surge system
to contacts
Reset/power down state:
No change - last state is retained
Inputs:
Number of inputs:
4
Sensing type:
Wet or dry contact status detection
Wetting voltage:
DC (1-24) V, internally generated
Input current:
2.5 mA – constant current regu-
lated
Minimum input voltage:
0 V (input shorted to common)
Maximum input voltage:
DC 150 V (diode protected against
polarity reversal)
Filtering:
De-bouncing with 50 ms delay time
Detection scan rate:
100 ms
Isolation:
AC 2500 V system to inputs
External Connection:
AWG 12-26/(0.129 - 3.31) mm
2
11 pin, 0.200” pluggable terminal
block
Mechanical Parameters
Dimensions:
7.6(L) x 11.28(W) x 4.36(H) in /
19.3(L) x 28.65(W) x 11.07(H) cm
Weight:
7 pounds (3.18 kg)