: MP200-S (Single Phase) Modbus Map
Doc# E166703 D-119
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
Range
Units or Resolution Comments
# Reg
Modbus Address
Hex
Decimal
7D21 - 7D21
32034 - 32034
In
p
ut Accumulators Scaling
UINT16
bit-ma
pp
ed
44443333 22221111
1
7D22 - 7D22
32035 - 32035
Relay Accumulators Scaling
UINT16
bit-ma
pp
ed
44443333 22221111
1
7D23 - 7D3E
32037 - 32063
Reserved
Set to 0.
8
7D3F - 7D46
32064 - 32071
In
p
ut#1 Label
ASCII
16 char
8
7D47 - 7D4E
32072 - 32079
In
p
ut#1 Low State Name
ASCII
16 char
8
7D4F - 7D56
32080 - 32087
In
p
ut#1 High State Name
ASCII
16 char
8
7D57 - 7D6E
32088 - 32111
In
p
ut#2 Label and State Names
24
7D6F - 7D86
32112 - 32135
In
p
ut#3 Label and State Names
24
7D87 - 7D9E
32136 - 32159
In
p
ut#4 Label and State Names
24
7D9F - 7DA6
32160 - 32167
Relay#1 Label
ASCII
16 char
8
7DA7 - 7DAE
32168 - 32175
Relay#1 O
p
en State Name
ASCII
16 char
8
7DAF - 7DB6
32176 - 32183
Relay#1 Closed State Name
ASCII
16 char
8
7DB7 - 7DCE
32184 - 32207
Relay#2 Label and State Names
24
7DCF - 7DFE
32208 - 32255
Reserved
Reserved
48
7DFF - 7E06
32256 - 32263
In
p
ut#1 Accumulator Label
ASCII
16 char
8
7E07 - 7E0E
32264 - 32271
In
p
ut#2 Accumulator Label
ASCII
16 char
8
7E0F - 7E14
32272 - 32277
In
p
ut#3 Accumulator Label
ASCII
16 char
8
7E15
7E1E
32278
32287
In
p
ut#4 Accumulator Label
ASCII
16 char
8
7E1F - 7E1F
32288 - 32288
In
p
ut#1 Accumulator Kt
UINT16
bit-ma
pp
ed
ddVVVVVV VVVVVVVV
1
7E20
7E20
32289
32289
In
p
ut#2 Accumulator Kt
UINT16
bit-ma
pp
ed
ddVVVVVV VVVVVVVV
1
KT
p
ower factor for the Pulse Out
p
ut
"V" is raw
p
ower value in Wh/
p
ulse
from 0 to 9999. "dd"=decimal
p
oint
p
osition: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
same as In
p
ut#1
same as In
p
ut#1
same as In
p
ut#1
same as Relay#1
4 bits
p
er in
p
ut or out
p
ut
accumulator
The nibble informs what should be
the scaling of the accumulator 0=no-
scaling, 1=0.1, 2=0.01, 3= 1m,
4=0.1m, 5=0.01m, 6=1u, 7=0.1u; the
value 15 disable the accumulator.
Exam
p
le: su
pp
ose that the internal
in
p
ut accumulator #1 is 12345, and
its corres
p
onding scaling setting is
“0011” (3 decimal). Then, the
accumulator will be read as:
Scaling 3, means 1m or 0.001.
Scaled accumulator = 12345 * 0.001
= 12 (Twelve).