• Interval Energy is the amount of energy consumed during the storage
interval. For example, if you choose a 15 minute interval (the typical set-
ting), the meter profiles the load used during the 15 minute period for
each storage period. This lets you trend and graph an energy use profile
for each meter (circuit).
• The MP200 metering system’s logging capability works with EIG’s Communicator
EXT
TM
and E-Billing EXT
TM
software applications to enable you to create detailed
usage reports for analysis and to easily generate sub-tenant billing. The digital
input accumulators can be used to accumulate pulses from other than electrical
energy usage, e.g., gas or condensate (steam); to offer you a multi-commodity
billing solution.
• Limit/Alarm log: This log provides the magnitude and duration of alarms that fall
outside of configured acceptable limits. Time stamps and alarm value are provided
in the log. Up to 16,382 events can be logged.
• I/O Change log: This log provides a time-stamped record of the Relay Output/Digi-
tal Input board’s output or input status changes. Up to 16,382 events can be
logged.
• System Events log: In order to protect critical billing information, the MP200 unit
records and logs the following information with a timestamp:
• Demand resets
• Password requests
• System startup
• Energy resets
• Log resets
• Log reads
• Programmable settings changes