Doc
#
E166703
E-22
E: Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Enable:
1 (Engage log)
Scope:
0 (Normal Mode)
---------------------------------------------------
Receive
:
0106C34F0180 (echo)
NOTE
: This engages the log for use on this COM Port, and latches the oldest record as
record index 0.
3. Read [0xC747, 16 registers], Availability is 0.
Send
:
0103 C747 0010
Command
:
Register Address:
0xC747
# Registers:
16
---------------------------------------------------
Receive
:
010320 00000100 00000064 0012 0002
0C0717101511 0C0718101511
0000000000000000
Data
:
Max Records:
0x100 = 256 records maximum.
Num Records:
0x64 = 100 records currently logged.
Record Size:
0x12 = 18 bytes per record.
Log Availability:
0x02 = 1, In use by COM2, USB (the current
port)
First Timestamp:
0x0C0717101511 = July 23, 2012, 16:21:17
Last Timestamp:
0x0C0717101511 = July 24, 2012, 16:21:17
NOTE
: This indicates that the log has been engaged properly in step 2. Proceed to
retrieve the log.