D
: MP200-S (Single Phase) Modbus Map
Doc# E166703 D-118
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
Range
Units or Resolution Comments
# Reg
Modbus Address
Hex
Decimal
First Overlay
write only in PS update mode
7D00 - 7D00
32001 - 32001
In
p
ut#1 - 4 bindings & logging
enables
UINT16
bit-ma
pp
ed
44443333 22221111
One nibble for each in
p
ut.
Assuming "abcc" as the bits in each
nibble:
"a": select this in
p
ut for EOI (End Of
Interval)
p
ulse sensing.
"b": log this in
p
ut when
p
ulse is
detected
"cc": In
p
ut event trigger mode -
Contact sensing method; 00 =
none; 01 = o
p
en to close; 10 = close
to o
p
en; 11 = any change.
Every in
p
ut has an associated
internal accumulator (See in
p
ut
Accumulator Scaling), which is
incremented every time the in
p
ut
changes according with the trigger
mode crieteria “cc”
1
7D01 - 7D01
32002 - 32002
Relay #1 Delay to O
p
erate
UINT16
0.1 second
units
Delay to o
p
erate the relay since
request.
1
7D02 - 7D02
32003 - 32003
Relay #1 Delay to Release
UINT16
0.1 second
units
Delay to release the relay since
request.
1
7D03 - 7D08
32004 - 32009
Reserved
UINT16
Set to 0.
6
7D09 - 7D09
32010 - 32010
Relay #2 Delay to O
p
erate
UINT16
0.1 second
units
Delay to o
p
erate the relay since
request.
1
7D0A - 7D0A
32011 - 32011
Relay #2 Delay to Release
UINT16
0.1 second
units
Delay to release the relay since
request.
1
7D0B - 7D20
32012 - 32033
Reserved
UINT16
Set to 0.
22
Settings Registers for Digital I/O Relay Card