4-3-4. Formula to plan the precise weighing system
This “SI 4300” weighing controller’s Max. input sensitivity is
0.2
㎶
/ Digit
.
And for precise weighing system, the following formula must be satisfied.
Caution
: “Input sensitivity” means Min. output voltage variation of weighing part to change 1digit.
So, please do not make large input voltage to make reliable weighing system.
≤
E B D
ⅹ ⅹ
0.2
㎶
Single Load cell use
A
≤
E B D
ⅹ ⅹ
0.2
㎶
Plural Load cells use
A N
ⅹ
A : Load cell capacity(kg)
B : Load cell Voltage(mV)
D : Digit
E : affirmation Voltage of Load cell
N : Number of Load cell
Example1.)
Number of Load cell : 1pcs
Load cell capacity : 500kg
Load cell Voltage : 2mV/V
Digit : 0.05kg
Affirmation Voltage of Load cell : 5,000mV
Max. Capacity of Weighing System : 300kg
Then, estimation result for this weighing system with formula,
5000 2 0.05
ⅹ ⅹ
500
= 1
≥
0.2
㎶
The calculated value is larger than 0.2
㎶
, so this
system has no problem.
Example2.)
Number of Load cell : 4pcs
Load cell capacity : 500kg
Load cell Voltage : 2mV/V
Digit : 0.10kg
Affirmation Voltage of Load cell : 5,000mV
Max. Capacity of Weighing System : 1,000kg
Then, estimation result for this weighing system with formula,
5000
ⅹ
2
ⅹ
0.10
500 4
ⅹ
= 0.5
≥
0.2
㎶
The calculated value is larger than 0.2
㎶
, so
this system has no problem.