![SEW Movitrac B Скачать руководство пользователя страница 235](http://html1.mh-extra.com/html/sew/movitrac-b/movitrac-b_operation-instructions-manual_1250009235.webp)
Operating Instructions – MOVITRAC® B
235
8
Technical data for braking resistors, chokes and filters
Technical data
Output filter type
HF075-503
1)
HF023-403
1)
HF033-403
1)
HF047-403
1)
HF450-503
HF180-403
Part number
826 313 2
825 784 1
825 785 X
825 786 8
826 948 3
0 829 909 9
Nominal voltage V
N
3 × AC 230 – 500 V, 50/60 Hz
2)
Leakage current at V
N
∆
I
0 mA
Power loss at I
N
P
V
135 W
90 W
120 W
200 W
400 W
860 W
Interference emission via
unshielded motor cable
According to limit value class C1/C2 in accordance with EN 61800-3
3)
Ambient temperature
ϑ
amb
0 °C to +45 °C (reduction: 3% I
N
per K to max. 60 °C)
-25 °C to +85 °C
Degree of protection (EN 60529)
IP20
IP20
IP10
IP00
Connections /
Tightening torque
M4 terminal
stud
1.6 Nm ±
20%
35 mm
2
(AWG 2)
3.2 Nm
M10 terminal studs /
70 mm
2
(AWG 3/0) 30 Nm
(270 lb in)
Mass
10.8 kg
(23.8 lb)
15.9 kg (35.1
lb)
16.5 kg
(36.4 lb)
23 kg
(51 lb)
32 kg
(71 lb)
85.3 kg
(188 lb)
Assignment of AC 400/500 V units
Voltage drop at I
N
∆
U
< 6.5% (7.5%) at AC 400 V / < 4% (5%) at AC 500 V at f
Amax
= 50 Hz (60 Hz)
Nominal through current I
N 400 V
(at V
line
= 3 × AC 400 V)
Nominal through current I
N 500 V
(at V
line
= 3 × AC 500 V)
AC 16 A
AC 13 A
AC 23 A
AC 19 A
AC 33 A
AC 26 A
AC 47 A
AC 38 A
AC 90 A
AC 72 A
AC 180 A
AC 180 A
Nominal operation (100%)
3)
0075
0110
0150/0300
0220
0370/0450/
0550
4)
/0750
0550/0750
Increased power (125%)
3)
0055
0075
0110/0220
0150
0300/0370/0
450
/0550/0750
0550/0750
Assignment to AC 230 V units
Voltage drop at I
N
∆
U
< 18.5% (19%) at AC 230 V with f
Amax
= 50 Hz (60 Hz)
Nominal through current I
N 230 V
(at V
line
= 3 × AC 230 V)
AC 29 A
AC 42 A
AC 56.5 A
AC 82.6 A
AC 156 A
-
Nominal operation (100%)
3)
0075
0110
0150/0300
0220
0300
-
Increased power (125%)
3)
0055
0075
0110/0220
0150
0220/0300
-
1) Approved to UL/cUL in conjunction with MOVITRAC
®
inverters. SEW-EURODRIVE provides proof of approval on request.
2) A reduction of 6% I
N
per 10 Hz applies above f
A
= 60 Hz for the nominal through current I
N
.
3) Observe the chapter on EMC-compliant installation according to EN 61800-3 in the SEW documentation
4) Connect 2 HF...-... output filters in parallel for operation on these MOVITRAC
®
units.
P
i
f
kVA
Hz
n
Содержание Movitrac B