![SEW Movitrac B Скачать руководство пользователя страница 194](http://html1.mh-extra.com/html/sew/movitrac-b/movitrac-b_operation-instructions-manual_1250009194.webp)
194
Operating Instructions – MOVITRAC® B
8
Technical data for accessories and options
Technical data
DFE33B fieldbus interface for EtherNet/IP and Modbus/TCP
Description
With the powerful, universal fieldbus interface option EtherNet/IP DFE33B, the
MOVITRAC
®
B frequency inverter can be connected to higher-level automation sys-
tems via EtherNet/IP.
Refer to the publication "DFE33B EtherNet/IP Fieldbus Interface" for installation.
Electronics data
DFE33B option
External voltage
supply
U = DC 24 V (–15%, +20%)
I
max
= DC 200 mA
P
max
= 3.4 W
Application proto-
cols
•
EtherNet/IP
(Industrial Protocol) or
Modbus/TCP
to control
and parameterize the inverter.
•
HTTP
(Hypertext Transfer Protocol) for diagnostics using a
Web browser.
•
SMLP
(Simple MOVILINK Protocol), protocol used by
MOVITOOLS
®
MotionStudio.
•
DHCP
(Dynamic Host Configuration Protocol) to assign
address parameter automatically.
Port numbers used
•
44818 EtherNet/IP (TCP)
•
2222 EtherNet/IP (UDP)
•
502 Modbus/TCP
•
300 SMLP (TCP, UDP)
•
80 HTTP
•
67 / 68 DHCP
Ethernet services
•
ARP
•
ICMP (ping)
ISO/OSI layer 1/2
ISO/OSI layer 4/5
•
Ethernet II
•
TCP/IP and UDP/IP
Automatic baud
rate detection
10 / 100 MBd
Connection tech-
nology
2 × RJ45 with internal switch and auto crossing
Addressing
4 byte IP address and/or MAC ID (00-0F-69-xx-xx-xx)
Manufacturer ID
(Vendor ID)
•
013B
hex
(EtherNet/IP)
•
"SEW-EURODRIVE" (Modbus/TCP)
Tools for startup
MOVITOOLS
®
MotionStudio version 5.40 and higher.
Firmware version
of MOVITRAC
®
B
No special firmware is required.
EDS file name
SEW_GATEWAY_DFE33B.eds
DFE33B
ETHERNET/IP
MODULE
STATUS
NETWORK
STATUS
xx
xx
xx
xx
P
i
f
kVA
Hz
n