![SEW-Eurodrive MOVIPRO ADC Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/sew-eurodrive/movipro-adc/movipro-adc_operating-instructions-manual_1250122065.webp)
7
Electrical installation
Using prefabricated cables
Operating Instructions – MOVIPRO
®
ADC
65
7.9
Using prefabricated cables
SEW‑EURODRIVE uses prefabricated cables for certifications, type tests and ap-
proval of the devices. The cables provided by SEW‑EURODRIVE fulfill all require-
ments necessary to ensure that the device and all connected components function
properly. The devices under consideration are always the basic devices including all
connected components and corresponding connection cables.
This is why SEW‑EURODRIVE recommends to use only the prefabricated cables spe-
cified in the documentation.
In accordance with EN ISO 13849, when using devices with integrated safety func-
tions, you must also adhere to all of the conditions and requirements for the installa-
tion and routing of cables described in the corresponding device’s functional safety
documentation.
7.9.1
Use of third-party cables
If third-party cables are used – even if these cables are technically equivalent –
SEW‑EURODRIVE will not accept any liability and cannot guarantee compliance with
device properties or that the device will function correctly.
When using third-party cables to connect the device and/or device components, make
sure to comply with all applicable national regulations. Note that the technical features
of the device or system of devices might be affected inadvertently when using non-
SEW cables. This concerns in particular the following properties:
•
Mechanical properties (such as IP protection class, cable carrier suitability)
•
Chemical properties (such as the absence of silicone and halogen, resistance
against substances)
•
Thermal properties (e.g. temperature stability, heating of the device, flammability
class)
•
EMC behavior (such as interference emission limit values, compliance with inter-
ference immunity values stipulated in standards)
•
Functional safety (approvals according to EN ISO 13849-1)
Non-SEW cables not explicitly recommended by SEW‑EURODRIVE must meet at
least the requirements of the following standards and have been permitted according
to these standards:
•
IEC 60309
•
IEC 61984
•
IEC 60204
7.10
Line components
7.10.1
Residual current device
WARNING
No protection against electric shock if an incorrect type of residual current device is
used.
Severe or fatal injuries.
•
Use only universal current sensitive residual current devices of type B for 3-
phase frequency inverters.