9
Operation
Status and error messages
Operating Instructions – MOVIPRO
®
ADC
173
Status LEDs
The status LEDs are located on the service unit. They show the fieldbus and device
status.
[1]
1954344587
[1]
Status LEDs S1, S2, S3
Status LED S1 PROFINET IO
StatusLED
Possible cause
Measure
Off
•
PROFINET IO device is cur-
rently exchanging data with
the PROFINET IO controller
(Data Exchange).
–
Flashing
green
Flashing
green/red
•
The flashing function in the
PROFINET IO controller con-
figuration is activated to visu-
ally locate the stations.
–
Lights up red •
Connection to the PROFINET
IO controller has failed.
•
PROFINET IO device does
not detect a link.
•
Bus interruption
•
PROFINET IO controller is not
in operation.
•
Check the PROFINET con-
nection of the device.
•
Check the PROFINET IO con-
troller.
•
Check the cabling of your
PROFINET network.
Flashing yel-
low
Lights up yel-
low
•
The STEP 7 hardware config-
uration contains a module that
is not permitted.
•
Set the STEP 7 hardware
configuration to ONLINE. Ana-
lyze the component status of
the slots in the PROFINET IO
device.
Status LED S1 PROFIBUS
Status LED
Possible cause
Measure
Off
Device is currently exchanging
data with the DP master (data ex-
change).
–
22749055/EN – 04/2016