MOVIDRIVE
®
MD_60A Operating Instructions
63
Complete parameter list
8__
UNIT FUNCTIONS
80_
Setup
802/ Factory setting
YES / NO
803/ Parameter lock
ON / OFF
804
Reset statistic data
NO FAULT MEMORY
KWH-METER
OPERATING HOURS
800/ Quick menu
ON / OFF
These parameters are only available in the DBG11A keypad, not in
MOVITOOLS!
801/ Language
DE / EN / FR
806
Copy DBG
→
MDX
YES / NO
807
Copy MDX
→
DBG
YES / NO
81_
Serial communication
810
RS485 address
0 – 99
811
RS-485 group address 100 – 199
812
RS485 timeout delay
0 – 650 s
813
SBus address
0 – 63
814
SBus group address
0 – 63
815
SBus timeout delay
0 – 0.1 – 650 s
816
SBus baud rate
125/250/500 / 1000
kbaud
817
SBus synchronization
ID
0 – 1023
818
CAN synchronization
ID
0 – 1 – 2047
819
Fieldbus timeout delay 0 – 0.5 – 650 s
82_
Brake operation
820/
4-quadrant
operation 1
ON / OFF
821
4-quadrant
operation 2
ON / OFF
83_
Fault response
830
response
EXT. FAULT
EMERG.STOP/FAULT
The following fault responses can be programmed: NO
RESPONSE
•
DISPLAY FAULT
•
IMM. STOP/FAULT
•
EMERG.STOP/FAULT
•
RAPID STOP./FAULT
•
IMM. STOP/
WARNG
•
EMERG. STOP/WARNG
•
RAPID STOP/WARNG
831
Response
FIELDBUS TIMEOUT
RAPID STOP/WARNG
832
Response
MOTOR OVERLOAD
EMERG.STOP/FAULT
833
Response
RS485 TIMEOUT
RAPID STOP/WARNG
834
Response DRS LAG
ERROR
EMERG.STOP/FAULT
835/
Response
TF sensor SIGNAL
NO RESPONSE
836
Response
SBus TIMEOUT
EMERG.STOP/FAULT
84_
Reset response
840/ Manual reset
YES / NO
841
Auto reset
ON / OFF
842
Restart time
1 – 3 – 30 s
85_
Scaling speed actual value
850
Scaling factor
numerator
1 – 65535
Can only be set using MOVITOOLS
851
Scaling factor
denominator
1 – 65535
852
User dimension
1 rpm
Par.
Name
Setting range
Factory setting
After
startup
Par.
Name
Setting range
Factory setting
After
startup
Variable par.
Parameter set 1
Parameter set 2
0
0
I