50
MOVIDRIVE
®
MD_60A Operating Instructions
Startup with the DBG11A keypad
11. If no TF/TH is connected to X10:1 and X10:2
→
Set "NO
RESP.". Set the required fault response if a TF/TH is
connected.
835*
NO RESP.
RESP. TF sens SIGNAL
12. Commence the startup calculation by selecting "YES".
C06*
NO
CALCULATION
WITH SEW MOTORS
13. The calculation is performed.
WITH NON-SEW MOTORS
13. The calculation for non-SEW motors requires a calibration
procedure:
•
When prompted, give a "1" signal on terminal X13:1 (DIØØ
"/CONTROL.INHIBIT").
•
Give a "0" signal on terminal X13:1 again after the
calibration is complete.
•
The motor parameters are estimated if it is not possible to
calibrate (energize) the motor.
14. The "SAVE" menu command appears automatically. The
keypad is already in edit mode.
C08*
_NO
SAVE
15. Set "SAVE" to "YES". The data (motor parameters) are copied
into the non-volatile memory of MOVIDRIVE
®
.
DATA ARE BEING
COPIED...
16. This completes the startup. Press the E or Q key to exit the
startup menu. The main display then appears.
CONTROL.INHIBIT
CURRENT:
0
A
•
Copy the parameter set from MOVIDRIVE
®
into the DBG11A keypad after
completing the startup (P807 "MDX
→
DBG"). In this way, it is possible to use the
DBG11A to transfer the parameter set to other MOVIDRIVE
®
units (P 806 "DBG
→
MDX").
•
Enter any parameter settings which differ from the factory settings in the parameter
list (
→
page 280).
•
In the case of non-SEW motors, set the correct brake reaction time (P732 / P735).
•
Refer to the information in Sec. "Starting the motor" (
→
page 277) for starting the
motor.
•
With
∆
connection and transition point at 87 Hz
→
Set parameter P302/312
"Maximum speed 1/2" to the value for 87 Hz.