MD_60A Operating Instructions
2
Safety Notes
Installation and
startup
•
Never install damaged products or take them into operation.Please submit a
complaint to the transport company immediately in the event of damage.
•
Installation, startup and service work only by trained personnel observing
applicable accident prevention regulations and operating instructions! The
regulations in force (e.g. EN 60204, VBG 4, DIN-VDE 0100/0113/0160) must also be
complied with.
•
Follow the specific instructions during installation and startup of the motor and
the brake!
•
The unit meets all requirements for reliable isolation of power and electronics
connections in accordance with EN 50178. All connected circuits must also satisfy
the requirements for reliable isolation so as to guarantee reliable isolation.
•
Take suitable measures (e.g. disconnecting the electronics terminal block) to
ensure that the connected motor does not start up automatically when the inverter
is switched on.
Operation and
servicing
•
Disconnect the unit from the supply system prior to removing the protective
cover. Dangerous voltages may still be present for up to 10 minutes after mains
disconnection.
•
Dangerous voltages are present at the output terminals and the cables and
motor terminals connected to them when the unit is switched on. This also
applies even when the unit is inhibited and the motor at a standstill.
•
Just because the operation LED and other display elements have gone out does
not mean that the unit has been disconnected from the supply system and is de-
energized.
•
The inverter output may only be switched when the output stage is inhibited.
•
Make sure that preventive measures and protection devices correspond to the
applicable regulations (e.g. EN 60204 or EN 50178).
Required preventive measures:
Grounding the unit
Required protection device:
Overcurrent protection devices
•
The unit has IP 00 enclosure with the protective cover removed. Dangerous
voltages are present on all subassemblies except for the control electronics. The
unit must be closed during operation.
•
Safety functions inside the unit or a mechanical blockage may cause the motor
to stop. The removal of the source of the malfunction or a reset can result in an
automatic restart of the drive. If, for safety reasons, this is not permissible for the
driven machine, the unit must be disconnected from the supply system before
correcting the fault. In such cases, it is also forbidden for the "Auto reset" function
(P841) to be activated.