Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
53
9
Configuring a PROFIBUS DP master
Configuration and Startup on the PROFIBUS DP-V1 Fieldbus
9
Configuration and Startup on the PROFIBUS DP-V1 Fieldbus
9.1
Configuring a PROFIBUS DP master
You need a GSD file to configure a PROFIBUS DP master for controlling MOVI-PLC
®
advanced
DHF41B.
GSD file for
PROFIBUS
DP/DP-V1
The
GSD file SEW_6007.GSD
corresponds to GSD revision 4. The device master data
files standardized by the PROFIBUS user organization can be read by all PROFIBUS
DP masters.
General project
planning
procedure
Proceed as follows to configure the MOVI-PLC
®
advanced
DHF41B control card with
PROFIBUS DP interface:
1. Install (copy) the GSD file according to the requirements of your configuration
software (see manuals of your configuration software or the section "Installing the
GSD file in STEP7", below). Once the file has been installed properly, the device
appears next to the slave stations with the designation
MOVI-PLC
.
2. For configuration, add the MOVI-PLC
®
advanced
DHF41B control card under the
name
MOVI-PLC
to the PROFIBUS structure and assign the PROFIBUS station
address.
3. Select the process data configuration required for your application (see section "DP
Configurations").
4. Enter the I/O or peripheral addresses for the configured data widths.
After configuration, you can start PROFIBUS DP. The red
Fault PROFIBUS
LED
indicates the status of the configuration (OFF = configuration OK).
TIP
The current version of the GSD file for controlling MOVI-PLC
®
advanced
DHF41B is
available on the SEW website (http://www.sew-eurodrive.de) in the "Software" section.
Configuration tool
DP master
File name
All DP configuration tools to IEC 61158
For DP master
standard
SEW_6007.GSD
Siemens S7 hardware configuration
For all S7 DP masters
TIP
Do not change or expand entries in the GSD file! SEW assumes no liability for
malfunctions that occur in MOVI-PLC
®
or connected inverters if a GSD file has been
modified!