Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
41
6
The Common Industrial Protocol (CIP)
DeviceNet Operating Characteristics
Parameter object
• The fieldbus parameters of the MOVI-PLC
®
advanced
DHF41B can be addressed
directly via the instance with the parameter object.
• In exceptional cases, you can also use the parameter object to access SEW
parameters.
• Class code: 0F
hex
Class
Instance 1 - 133
Instances 1 - 133 provide access to the fieldbus parameters.
Attribute
Access Name
Data type
Default value
[hex]
Description
2
Get
Max Instance UINT
0085
Maximum instance = 133
8
Get
Parameter
Class
Descriptor
UINT
0009
Bit 0: Supports parameter instances
Bit 3: Parameters are saved
permanently
9
Get
Configura-
tion Assem-
bly Interface
UINT
0000
Configuration assembly is not
supported.
Attribute Access
Name
Data type
Default value
[hex]
Description
1
Set/Get
Parameter
UINT
Parameter to be read or written (see
section "Fieldbus parameters
MOVI-PLC
®
advanced
DHF41B")
2
Get
Link Path
Size
USINT
00
No link is specified.
3
Get
Link Path
Packed
EPATH
00
Not used
4
Get
Descriptor
WORD
0000
Read/write parameter
5
Get
Data type
EPATH
00C8
UDINT
6
Get
Data Size
USINT
04
Data length in bytes
0
0
I