![SEW-Eurodrive DHF41B Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/sew-eurodrive/dhf41b/dhf41b_manual_1250085013.webp)
Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
13
4
Setting the DIP switches
Assembly and Installation Notes on the DeviceNet Fieldbus
4.5
Setting the DIP switches
Setting the
MAC-ID
The MAC ID (
M
edia
A
ccess
C
ontrol
Id
entifier) is set on the DHF41B option using DIP
switches 2
0
- 2
5
in a binary coded manner. The MAC-ID represents the node address of
the DHF41B. The DHF41B supports the address range 0 - 63.
Setting the baud
rate
The baud rate is set using DIP switches 2
6
and 2
7
.
A maximum of 64 DeviceNet data words can be exchanged between the DeviceNet
module and the DHF41B option. The number is set from the IEC program either using
the MC_DeviceNetPDConfig function block or the DeviceNet scanner.
TIP
Before each change to the DIP switches, disconnect MOVI-PLC
®
advanced
DHF41B
from the voltage supply. The DIP switch settings are adopted during initialization only.
63210AXX
2
0
- 2
5
= MAC ID setting
2
6
- 2
7
= Baud rate setting
DHF41B
2
2
2
2
0
1
2
3
2
2
2
4
5
6
27
ON
DIP switch
Baud rate
2
6
2
7
0
0
125 kBd
1
0
250 kBd
0
1
500 kBd
1
1
Invalid