20
Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
5
Settings in MOVI-PLC® advanced DHF41B
Project Planning and Startup on the DeviceNet Fieldbus
In the parameter tree of MOVITOOLS
®
MotionStudio (index 8451), the currently set
value is displayed in the field "PD configuration" (see following figure).
The number of process data words received and sent via DeviceNet is set at the
ProcessData
input. The value entered here must match the number of I/O data, which
is configured in the DeviceNet scanner.
Refer to the IEC program and its documentation for information on whether and how the
transmitted process data words are used.
Parameterization using the
MC_DeviceNetPDConfig
function block in the IEC program
offers the advantage that the process data configuration is stored on the memory card
of the MOVI-PLC
®
advanced
DHF41B option together with the associated program.
5.3.2
Status of the fieldbus interface
The
FbusGetInfo
function block (or
ProfibusDeviceNetGetInfo
) makes the status and
some display parameters of the fieldbus interface available to the IEC program and for
diagnostic purposes.
If there is no communication with the fieldbus master, the output
Error
is set to
TRUE
.
During an active fieldbus connection, the output
Done
is set to
TRUE
, and the outputs
Address
,
Baud rate
,
Timeout
and
Bus type
show the respective parameters as they
were set via the DIP switches of the DHF41B option or via the PLC.
11968AXX
12046AXX
0
0
I