6
Operation
Operating display (LEDs)
Operating Instructions – MOVI4R-U
®
Frequency Inverter Module
24
6.2
Operating display (LEDs)
The following figure shows the LEDs of the MOVI4R‑U
®
inverter:
DI03
Boost
n
n
max
n
x
2
N
P
Ι
U
[10]
[11]
[9]
[8]
[7]
[6]
[5]
[4]
[3]
[2]
[1]
N
9290647051
[1] – [10]
LED 1 – 10
[11]
Status LED
6.2.1
LED 1 – 10
LEDs 1 – 10 are used to visualize the functions, setpoints, actual values and parame-
ters. It is for this reason that the LED display depends on the current status of the
MOVI4R‑U
®
inverter.
LED
1 – 10
Operating status MOVI4R‑U
®
inverter
Response
display
Lights up
(1 LED)
Level 1
No. of function
Lights up
(bargraph display)
Setting a setpoint,
display of an actual value
Setpoint/actual value
Flashing
(400 ms on)
(100 ms off)
Setting a parameter
Parameter value
Flashing
(100 ms on)
(400 ms off)
A fault occurred.
See chapter "Fault list
MOVI4R‑U
®
".
No. of fault code
Refer to the “Functions” chapter for more information on the meaning of the LEDs.
6.2.2
Status LED
The status LED shows the current status of the MOVI4R‑U
®
inverter:
Status LED
Meaning
Off
No voltage supply.
Yellow
MOVI4R-U
®
inverter is ready for operation.
Green
MOVI4R-U
®
inverter is enabled.
28520688/EN – 12/2018