background image

 

Start-Up  

 

To begin, place the bypass in the position shown in Figure 1.  

 

Place the softener in the Backwash cycle. 

To place the softener in the Backwash cycle press 

and hold the REGEN button (approx. 6 seconds) until 

the control valve initiates a regeneration cycle. The 

softener is now in the Backwash cycle. An initial burst 

of air will be released to the drain. Leave the unit in 

the Backwash cycle until the water running to the 

drain runs clear. 

Press the REGEN button to advance the controller to 

the next cycle. The softener is now in the Brine/Slow 

Rinse cycle.  

When the timer begins countdown press the REGEN 

button to advance the controller to the next cycle. The 

softener is now in the 2nd Backwash cycle.  

When the timer begins countdown press the REGEN 

button to advance the controller to the next cycle. The 

softener is now in the Fast Rinse cycle. Leave the 

unit in the Fast Rinse cycle for at least five minutes.  

While the system is rinsing manually fill the brine tank 

with fresh water until there is approximately 2” of 

water above the false bottom. 

Press the REGEN button to advance the controller to 

the next cycle. The softener is now in the Brine Tank 

Fill cycle. Leave the unit in the Brine Tank Fill cycle 

for at least one minute. This will ensure that there is 

no air trapped in the brine tubing and valve. 

IMPORTANT: 
After the unit has filled for approximately 1 

minute, raise the float to shut off the flow of water 

and then check the float valve, brine tubing and 

connections for leaks. 

Press the REGEN button to advance the controller to 

the home position.  

Salt may be placed in the unit at this time. 

 

To complete the Start-up place bypass in the position shown 

in Figure 2 

 

Start-Up Instructions 

Figure 1 

Figure 2 

Содержание 960SM Series

Страница 1: ...Single Metered Water Softening System Owner s Manual Series 960SM...

Страница 2: ...ontents System Specifications and Warnings 3 Start Up Instructions 4 Series 960 Control Valve Programming 5 Manually Regenerating the Water Softener 8 Bypass Valve Operation 9 Troubleshooting the Cont...

Страница 3: ...ontrol valve and fittings are not designed to support the weight of the system or the plumbing Do not use Vaseline oils other hydrocarbon lubricants or spray silicone anywhere A silicone lubricant may...

Страница 4: ...n to advance the controller to the next cycle The softener is now in the Fast Rinse cycle Leave the unit in the Fast Rinse cycle for at least five minutes While the system is rinsing manually fill the...

Страница 5: ...5 Control Valve Programming Series 960 Control Valve Programming...

Страница 6: ...EXT and the UP Arrow buttons at the same time and hold for 3 seconds Step 2 Raw Water Hardness Adjust to the correct hardness by pressing the UP or DOWN arrow button Default setting 20 grains per gall...

Страница 7: ...time of day will flash indicating that it needs to be set Step 1 Press SET CLOCK Step 2 Current Time of Day Hours Adjust to the correct hour by pressing the UP or DOWN arrow button Press NEXT to go t...

Страница 8: ...the water you may want to manual regenerate the softener using the delayed regeneration method To initiate a delayed regeneration simply push the REGEN button one time Don t hold the button down REGE...

Страница 9: ...9 Bypass Valve Operation Normal Operation Bypass Operation Diagnostic Mode Shut Off Mode...

Страница 10: ...Connect Meter to three pin connection labeled METER on Circuit Board Remove and reconnect to ensure proper connection Restricted stalled Meter Turbine Remove Meter and check for rotation or foreign m...

Страница 11: ...place Damaged Seal and Spacer Stack Assembly Replace Seal and Spacer Stack Assembly Control valve body type and piston type mix matched Verify proper control valve body type and piston type match Foul...

Страница 12: ...12 OM A960SM Printed in the USA Version 160915 1...

Отзывы: