Relay Connection
Analogue Outputs (mA)
0V DC
24V DC
~
~
A1
A1
A2
A2
Example fit protection
diodes when switching
external DC loads.
Example fit protection
supressors when switching
external AC loads typical
device Farnell Ref 1438460
(0.22uF 47R X1)
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
Out
Return
TOC-625
Relay
Output
TOC-625
Relay
Output
TOC-625
Relay
Output
As standard the TOC-625 controller is equipped with two relay outputs. The function of these two relay
outputs can be user configured and is discussed in a later section. The relays are rated to operate 4A
non inductive loads. Typical wiring arrangements are indicated below and show typical methods to
protect the relays during installation.
External E-Stop
Fire Panel Interface
Example showing typical
connection to a fire system.
As standard the TOC-625 is equipped with three analogue outputs. By default these are configured
as 4-20mA current outputs. By request these can be set to 0-10V DC outputs during production. This
is a factory only setting. The following diagrams indicate the connections
+24V DC
0V DC
mA Sig 1
mA Sig 2
mA Sig 3
mA Analogue Output Interfaces
1
0V DC
Input 1
Input 2
Input 3
Chassis Gnd
TOC-625 Analogue
Outputs
Typical Interface Panel
Note this diagram shows the use of screened
cabling when interfacing signal cables. Signal
cables should be segregated from power and
control cables for best results.
18
28
TOC-625
DC SUPPLY
VOLTS
R (Ohms)
at Interface
Panel
200
800
Allowable
Operating
Region
Ώ
Ώ
Ώ
Ώ
Page 14 of 25