Channel 1
Address
Gas
Range
AL1
AL1 Type
AL1 Relay
AL2
AL2 Type
AL2 Relay
Analogue
Output
Channel
4101
Methane
100% LEL
20%
Rising Latch
1
50%
Rising Latch
2
C1
Channel Set Up Overview
The Channel Number as indicated on the TOC-625 display
The gas which this channels detector measures
The measurement range for this channel
The threshold limit for alarm level 1
The threshold limit for alarm level 2
Alarm Action (in this case the alarm latches once the threshold is exceeded
Alarm Action (in this case the alarm latches once the threshold is exceeded
Which relay activates when alarm 1 threshold is exceeded
Which relay activates when alarm 2 threshold is exceeded
Which analogue output relates to this channel.
Note there are three analogue outputs available on the TOC-625
The detector address for this channel. This address will be marked
on the cover of the detector itself
Using channel one as an example the following diagram explains a typical channel set up.
If the control panel has been shipped pre-configured then once correctly connected the system will be
operational. The controller should correctly cycle through each channel with no indicated errors.
Relay Test
The alarm relay outputs can now be connected (if they are being used). The relay outputs can be
forced on and off using the ‘test relay’ function (TEST RLY).
test rly
7 of 9
release
From Normal Operation press the function button until the display
alters to show ‘release button.
The system now requests a password. Enter 50 to enter the
Engineer Menu.
Press the function button until option 7 of 9, TST RLY is displayed.
Now hold down the button until prompted to release.
The display will now indicate Relay 1 On (and relay 1 should be
energised. At each press of the button each physical output is
energised in turn as indicated on the display as:
á
50
PASSWORD
test rly
7 of 9
tst rly
release
RELAY 1
ON
RELAY 2
ON
BUZZER
ON
LED PWR
ON
LED FLT
ON
LED AL
ON BACK RED
ON
BACK GRN
ON
BACK blu
ON
Each button press cycles through
the displays as listed. To exit, press
and hold the button until prompted
to release
Page 13 of 25