Specifications 

SI-100IM (Main Alarm Unit) 

Main CPU 

MKE02Z64 (32bit High Speed CPU) 

2  Input Power 

DC24V 

3  Output Power 

DC24V 

4  Input Power Display 

4Digit FND Digital Display 

5  Main Power Display 

Green LED Display, 18 Bar Graph 

6  Spare Power Display   

4Digit FND Digital Display, 18 Bar Graph 

7  Spare Power Monitoring 

Red LED Display 

8  Warning Alarm Display 

AU01

 ~ 

AU12

 Display consecutive changes of warning unit.) 

9  Spare Power Test 

Battery Test Switch 

10 

Alarm Output 

Alarm 1 SPDT Relay Dry contact Signal Output   
Alarm 2 SPDT Relay Dry contact Signal Output   
Alarm 3 SPDT Relay Dry contact Signal Output   
Selected output among DC12V Output Alarm1 to 3 

11  Operation Power 

DC12V~DC28V (DC12V or less CPU Sleep Mode No Display) 

12  Size 

40(W) x 130(H) x104(D) 

13  Spare Power 

Ni-Cd Battery 18V 600mA (4Channel) 

**While the 24V.DC power is introduced for battery charge and discharge and for the power 
of  the  Alarm  Unit,  this  unit  can  make  an  alarm  generating  unit  display  by  communicating 
with the Alarm Unit and generate an alarm. 
SI-100IM Configuration and Description 

1.

 

4Digit FND Digital Display(Input Voltage: AC/DC)

 

2.

 

Green LED Display, 18 Input Voltage Bar Graph 

3.

 

Back-up  Power  Monitoring  Lamp  (Turned  off  when 
battery is disconnected.) 

4.

 

Switch  Caution  Lamp  (When  warning  is  activated, 
display buzzer stop) 

5.

 

Voltage Display 

6.

 

Power Lamp (POWER ICON) 

7.

 

Third warning Lamp based on SI-100IA configuration 

8.

 

Second warning Lamp based on SI-100IA configuration   

9.

 

First warning Lamp based on SI-100IA configuration.   

10.

 

Failure Lamp - Cable disconnection, Sensor defect 

11.

 

Back-up power test Switch (Check Battery connection) 

12.

 

Buzzer Stop Switch 

13.

 

Return  Switch  (When  buzzer  stops,  return  to  initial 
mode) 

Power

 

3rd

 

2nd

 

1st

 

Failure

 

Back-up 
Power

 

Switch 

 

Caution

 

Recovery

 

Buzzer Stop

 

Back-up Power 

Test

 

Содержание SI-100IA

Страница 1: ...I 100IM MAIN UNIT SI 100IA ALARM DISPLAY UNIT SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM SI 1 0 0 IA SI 1 0 0 IC U...

Страница 2: ...and Description 4 Product s Dimension 6 5 Internal Configuration 3 channel basis 7 6 Terminal Configuration 8 7 Product Instruction for Use 9 SI 100IM Main Alarm Unit SI 100IA Alarm Display Unit 8 Des...

Страница 3: ...chased a route that SENKO does not recognize a product with malfunction cannot be repaired or replaced free of charge when mechanical damages or deformations happen from improper use of the product by...

Страница 4: ...nnel display of a corresponding Alarm Unit on the Main Alarm Unit through the transmitted data so that a user at a glance can notice which alarm unit has given an alarm signal The three Alarm outputs...

Страница 5: ...4Channel While the 24V DC power is introduced for battery charge and discharge and for the power of the Alarm Unit this unit can make an alarm generating unit display by communicating with the Alarm U...

Страница 6: ...ale 13 Alarm Output Fault SPDT Relay Dry contact Signal Output ON OFF Alarm 1 SPDT Relay Dry contact Signal Output ON OFF Alarm 2 SPDT Relay Dry contact Signal Output ON OFF Alarm 3 SPDT Relay Dry con...

Страница 7: ...IMENSION SI 1 0 0 IA SI 1 0 0 IM 3 3 1 2 1 2 V PPM LEL 130 40 110 130 40 SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM...

Страница 8: ...r Switch 8 Built in BATTERY 9 SMPS 24V DC Power Supply 3CH 1 2A 6CH 2 2A 10CH 3 2A 12CH 4 5A 10 FRONT DOOR LINE LOAD ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND F...

Страница 9: ...OUT 4 20mA GND FAULT ALARM 3 ALARM 2 ALARM 1 ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V GAS DETECTOR MAIN UNIT SI 100IM ALARM UNIT SI 100IA 24V 4 20mA GND 3Wire 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND...

Страница 10: ...Unit SI 100IA Alarm Display Unit When the power is turned on the device will display the product software version 1 00 A for 1 sec and an ID of the Unit from 01 to 12 seconds for 4 seconds Then after...

Страница 11: ...efault 15 AL 2 Secondary Alarm Setting Value default 50 AL 3 Tertiary Alarm Setting Value default 70 Span Concentration of Calibration Gas default 25 N AL The number of calibration depending on the ca...

Страница 12: ...rm the device will display the voltage in process of charging and tell you about a state of charging spare power or a state of fully charged Return Switch Once you solve the problem with the gas detec...

Страница 13: ...ration bar graph will arise just as shown in the figures As a concentration rises as shown in the figures the primary secondary and tertiary alarm lamp will be turned on according to an alarm value th...

Страница 14: ...ill be changed Gas Calibration After adjusting the calibration gas concentration SCAL will be displayed If you press the Switch at this status a current gas value will be displayed Zero will be displa...

Страница 15: ...at once Secondary Alarm Value Change default 50 LEL Press the setting switch while AL 2 is shown a default number will be displayed If you need a change while a number is marked change the number by p...

Страница 16: ...ration Range LOW RANGE default 0 Press the Setting Switch when LRNG is displayed and a default value will be displayed Press the UP and DOWN Switch while a figure is being displayed You can change its...

Страница 17: ...when an alarm concentration level is reached Change in 12V Voltage Output default 321 17Press the Setting Switch when 12VO is displayed and a default value will be displayed Press the UP and DOWN Swit...

Страница 18: ...rmal range the alarm and the output will be still stored Even If the device is interlocked with other equipment and thus alarm is repeatedly on and off depending on a concentration a value can changed...

Отзывы: