9. Changes in the Internal Settings 

 

* Setting changes are available only for SI-100IA (Alarm Display Unit.) 

    1-1 

Gas Alarm Concentration Calibration   

 

If you hold the setting switch for 5 seconds, then 

Zero calibration 

  press a switch labeled as oFSt again, a current concentration will be displayed. 

(If a current concentration value is less than 0, it will be displayed as -) If the 
current concentration is not zero, press the setting button for  more than 1 
second. Then 

Ξ

SET will be flashing while the current value is adjusted to zero. 

 
(A value of LNG and LPG will turn into -0.9 at the time of Zero calibration and a value in the case of the LIN 
will be stored at the moment you press the setting button) 

Adjusting a concentration of calibration gas (default 25% LEL) 

When the Zero calibration is over and the SET is completed, the display will 
show  SPAN.  If  you  press  the  Switch  while  SPAN  is  being  displayed,  a 
concentration of the calibration gas that has been set will be displayed. If a 

concentration  of  the  calibration  gas  is  different,  enter  the  same  number  as 
that  of  the  calibration  gas  by  using  the  UP  and  DOWN  key  and  hold  the 
switch for 1 second at a status of a changed figure. Then the calibration gas 
concentration will be changed.

 

Gas Calibration 

After adjusting the calibration gas concentration, SCAL will be displayed. If 
you  press  the  Switch  at  this  status,  a  current  gas  value  will  be  displayed.   
(Zero will be displayed if the Zero calibration is completed). At this moment, 
inject the calibration gas to the sensor at this state.

 

If there is small change even after the gas is injected for 30 seconds, press 

the  setting  switch  for  more  than  one  second  when  a  displayed  concentration  value  is  different 
from  that  of  the  calibration  gas.  Then  while 

ΞSET

  is  being  blinking,  the  connection  will  be 

corrected to that of the calibration gas 

* If a Concentration of the Calibration Gas is consistent with a gas concentration that you 

hold,  all  you  have  to  do  is  to  implement  the  gas  calibration.  For  this,  press  the  setting 
switch for 5 seconds, and choose 

OFST

SPAN

, or 

SCAL 

with Circuit Test Switch to modify 

only parts necessary. By default, a SPAN value is set to 25%. (in case of flammable gas) 

*. In case of incorrect operations due to the progress of calibration, turn the power ON / OFF 
while  holding  a  setting  and  return  switch  simultaneously.  And  then,  for  5  seconds, 

FACT

 

will be displayed and the device will turn into the initial state. (In this case, gas re-calibration 
is necessary) 
*. If you press the return switch while calibration is in-progress, your device will be switched 
back to a normal mode from the calibration mode. 

LEL

LEL

LEL

LEL

LEL

Содержание SI-100IA

Страница 1: ...I 100IM MAIN UNIT SI 100IA ALARM DISPLAY UNIT SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM SI 1 0 0 IA SI 1 0 0 IC U...

Страница 2: ...and Description 4 Product s Dimension 6 5 Internal Configuration 3 channel basis 7 6 Terminal Configuration 8 7 Product Instruction for Use 9 SI 100IM Main Alarm Unit SI 100IA Alarm Display Unit 8 Des...

Страница 3: ...chased a route that SENKO does not recognize a product with malfunction cannot be repaired or replaced free of charge when mechanical damages or deformations happen from improper use of the product by...

Страница 4: ...nnel display of a corresponding Alarm Unit on the Main Alarm Unit through the transmitted data so that a user at a glance can notice which alarm unit has given an alarm signal The three Alarm outputs...

Страница 5: ...4Channel While the 24V DC power is introduced for battery charge and discharge and for the power of the Alarm Unit this unit can make an alarm generating unit display by communicating with the Alarm U...

Страница 6: ...ale 13 Alarm Output Fault SPDT Relay Dry contact Signal Output ON OFF Alarm 1 SPDT Relay Dry contact Signal Output ON OFF Alarm 2 SPDT Relay Dry contact Signal Output ON OFF Alarm 3 SPDT Relay Dry con...

Страница 7: ...IMENSION SI 1 0 0 IA SI 1 0 0 IM 3 3 1 2 1 2 V PPM LEL 130 40 110 130 40 SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM...

Страница 8: ...r Switch 8 Built in BATTERY 9 SMPS 24V DC Power Supply 3CH 1 2A 6CH 2 2A 10CH 3 2A 12CH 4 5A 10 FRONT DOOR LINE LOAD ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND F...

Страница 9: ...OUT 4 20mA GND FAULT ALARM 3 ALARM 2 ALARM 1 ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V GAS DETECTOR MAIN UNIT SI 100IM ALARM UNIT SI 100IA 24V 4 20mA GND 3Wire 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND...

Страница 10: ...Unit SI 100IA Alarm Display Unit When the power is turned on the device will display the product software version 1 00 A for 1 sec and an ID of the Unit from 01 to 12 seconds for 4 seconds Then after...

Страница 11: ...efault 15 AL 2 Secondary Alarm Setting Value default 50 AL 3 Tertiary Alarm Setting Value default 70 Span Concentration of Calibration Gas default 25 N AL The number of calibration depending on the ca...

Страница 12: ...rm the device will display the voltage in process of charging and tell you about a state of charging spare power or a state of fully charged Return Switch Once you solve the problem with the gas detec...

Страница 13: ...ration bar graph will arise just as shown in the figures As a concentration rises as shown in the figures the primary secondary and tertiary alarm lamp will be turned on according to an alarm value th...

Страница 14: ...ill be changed Gas Calibration After adjusting the calibration gas concentration SCAL will be displayed If you press the Switch at this status a current gas value will be displayed Zero will be displa...

Страница 15: ...at once Secondary Alarm Value Change default 50 LEL Press the setting switch while AL 2 is shown a default number will be displayed If you need a change while a number is marked change the number by p...

Страница 16: ...ration Range LOW RANGE default 0 Press the Setting Switch when LRNG is displayed and a default value will be displayed Press the UP and DOWN Switch while a figure is being displayed You can change its...

Страница 17: ...when an alarm concentration level is reached Change in 12V Voltage Output default 321 17Press the Setting Switch when 12VO is displayed and a default value will be displayed Press the UP and DOWN Swit...

Страница 18: ...rmal range the alarm and the output will be still stored Even If the device is interlocked with other equipment and thus alarm is repeatedly on and off depending on a concentration a value can changed...

Отзывы: