Press the Setting Switch 

when “

PDLY”

 

is displayed, and a default value 

will be displayed Press the UP and DOWN Switch while a figure is being 
displayed. You can change its value. 

 

Primary Alarm Delay Time (default 0.5) 

17

Press the Setting Switch 

when “

DLY1”

 

is displayed, and a default value 

will be displayed Press the UP and DOWN Switch while a figure is being 
displayed. You can change its value. 

 

Secondary Alarm Delay Time (default 0.5) 

17

Press the Setting Switch 

when “

DLY2”

 

is displayed, and a default value 

will be displayed Press the UP and DOWN Switch while a figure is being 
displayed. You can change its value. 

 

Tertiary Alarm Delay Time (default 0.5) 

Press the Setting Switch 

when “

DLY3”

 

is displayed, and a default value 

will be displayed Press the UP and DOWN Switch while a figure is being 
displayed. You can change its value. 

 

*.  The  initial  delay  time  can  be  extended  into  more  than  30  seconds,  depending  on  the 
settling time of the sensor. 
*.  Delay  time  by  alarm  type  can  be  immediately  or  further  delayed  when  an  alarm 
concentration level is reached.   
 

Change in 12V Voltage Output (default 321) 

17

Press the Setting Switch 

when “

12VO”

 

is displayed, and a default value 

will be displayed Press the UP and DOWN Switch while a figure is being 
displayed. You can change its value. 

 

*. 321 (at primary, secondary and tertiary alarm, all can be output.) 
*. 32_ (only the secondary and tertiary alarm are output.) 
*.  3_1  (only  the  tertiary  and  the  primary  alarm  are  output.)  Likewise,  it  is  possible  to 
generate 12V selectively at the time of an alarm output. 
*. In the case of Main Alarm Unit (SI-100IM), 12V will be output depending on such a setting   

4-20mA output (default OFF) 

17

Press  the  Setting  Switch 

when  “

TSTO”

 

is  displayed,  and  a  default 

value will be displayed Press the UP and DOWN Switch while a figure is 
being displayed. You can change its value. 

 

*.This enables a user to choose whether or not the 4-20mA will be output at the circuit test 
or the gas reaction. *. By default, this will create an output at a reaction to gas. (If you make 
telecommunications by connecting an analog output to the plc or computer, there might be 
a case in which circuit test can be mistaken for a gas leak. -You need a careful attention. 
 

Alarm Return (default 321)

 

Содержание SI-100IA

Страница 1: ...I 100IM MAIN UNIT SI 100IA ALARM DISPLAY UNIT SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM SI 1 0 0 IA SI 1 0 0 IC U...

Страница 2: ...and Description 4 Product s Dimension 6 5 Internal Configuration 3 channel basis 7 6 Terminal Configuration 8 7 Product Instruction for Use 9 SI 100IM Main Alarm Unit SI 100IA Alarm Display Unit 8 Des...

Страница 3: ...chased a route that SENKO does not recognize a product with malfunction cannot be repaired or replaced free of charge when mechanical damages or deformations happen from improper use of the product by...

Страница 4: ...nnel display of a corresponding Alarm Unit on the Main Alarm Unit through the transmitted data so that a user at a glance can notice which alarm unit has given an alarm signal The three Alarm outputs...

Страница 5: ...4Channel While the 24V DC power is introduced for battery charge and discharge and for the power of the Alarm Unit this unit can make an alarm generating unit display by communicating with the Alarm U...

Страница 6: ...ale 13 Alarm Output Fault SPDT Relay Dry contact Signal Output ON OFF Alarm 1 SPDT Relay Dry contact Signal Output ON OFF Alarm 2 SPDT Relay Dry contact Signal Output ON OFF Alarm 3 SPDT Relay Dry con...

Страница 7: ...IMENSION SI 1 0 0 IA SI 1 0 0 IM 3 3 1 2 1 2 V PPM LEL 130 40 110 130 40 SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM...

Страница 8: ...r Switch 8 Built in BATTERY 9 SMPS 24V DC Power Supply 3CH 1 2A 6CH 2 2A 10CH 3 2A 12CH 4 5A 10 FRONT DOOR LINE LOAD ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND F...

Страница 9: ...OUT 4 20mA GND FAULT ALARM 3 ALARM 2 ALARM 1 ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V GAS DETECTOR MAIN UNIT SI 100IM ALARM UNIT SI 100IA 24V 4 20mA GND 3Wire 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND...

Страница 10: ...Unit SI 100IA Alarm Display Unit When the power is turned on the device will display the product software version 1 00 A for 1 sec and an ID of the Unit from 01 to 12 seconds for 4 seconds Then after...

Страница 11: ...efault 15 AL 2 Secondary Alarm Setting Value default 50 AL 3 Tertiary Alarm Setting Value default 70 Span Concentration of Calibration Gas default 25 N AL The number of calibration depending on the ca...

Страница 12: ...rm the device will display the voltage in process of charging and tell you about a state of charging spare power or a state of fully charged Return Switch Once you solve the problem with the gas detec...

Страница 13: ...ration bar graph will arise just as shown in the figures As a concentration rises as shown in the figures the primary secondary and tertiary alarm lamp will be turned on according to an alarm value th...

Страница 14: ...ill be changed Gas Calibration After adjusting the calibration gas concentration SCAL will be displayed If you press the Switch at this status a current gas value will be displayed Zero will be displa...

Страница 15: ...at once Secondary Alarm Value Change default 50 LEL Press the setting switch while AL 2 is shown a default number will be displayed If you need a change while a number is marked change the number by p...

Страница 16: ...ration Range LOW RANGE default 0 Press the Setting Switch when LRNG is displayed and a default value will be displayed Press the UP and DOWN Switch while a figure is being displayed You can change its...

Страница 17: ...when an alarm concentration level is reached Change in 12V Voltage Output default 321 17Press the Setting Switch when 12VO is displayed and a default value will be displayed Press the UP and DOWN Swit...

Страница 18: ...rmal range the alarm and the output will be still stored Even If the device is interlocked with other equipment and thus alarm is repeatedly on and off depending on a concentration a value can changed...

Отзывы: