SI-100IM (Main Alarm Unit) 

When the power switch is ON, an AC / DC voltage according to an input 

voltage and a bar graph according to a voltage level will be displayed. An 
arrow  on  the  side  of  the  bar  graph  indicates  a  voltage  range  of  the 
products at its operational status.   
Turn on the  battery switch (back-up power) on the back of the product, 
and spare power lamp will be extinguished and the device will enter into 
a  normal  state.  If  you  press  the  back-up  power  switch  to  find  a  spare 
power status, the device will display a DC voltage and a charging voltage 
will  be  displayed.  When  an  alarm  occurs,  the  power  indication  unit  will 
display  the  ID  of  the  Alarm  Unit.  According  to  primary,  secondary  and 
tertiary alarm set in the alarm, an alarm icon will be blinking. (An ID will 
be displayed alternating if alarms occur in many places.) When an alarm 
occurs, you can press the buzzer stop switch to mute the sound. 
If you press the Return button when the alarm condition is released, the 
alarm  icon  and  all  operations  will  turn  into  a  normal  status.  Because 
turning  on  the  failure  icon  may  be  caused  by  failure of  the  Alarm  Unit, 
you need to check the Alarm Unit. 
 

SI-100IA (Alarm Display Unit)

 

When the power is turned on, the device will display the product software 
version (1.00.A) for 1 sec and an ID of the Unit from (01) to (12) seconds 
for 4 seconds. Then, after 25 seconds of stabilization, a corresponding gas 
density will be displayed. When the Power icon is turned on after flashing 
during initial  stabilization time (30 seconds), the  device will enter into a 
normal operation (If 

ErrL

 is displayed and an alarm emits, the wiring in 

the  detection  unit  is  defective  or  has  bad  connection.  If  the  sensor  is 
defective, you need to have the device checked). If a gas leakage happens, 
the  gas  concentration  will  go  up  according  to  the  changes  in  a 
corresponding gas concentration and a bar graph will be also pushed up 
by  a  concentration.  As  a  concentration  rises,  1

ST

,  2

nd

,  3

rd

  alarm  will  be 

generated  according  to  an  alarm  setting  value,  thereby  making  a 
corresponding signal output (12V, Dry Contact, 4-20mA). With the circuit 
test switch, you can test a status of the product in normal concentration 
state. When you press the test circuit for a second, the concentration bar 
graph will go up, thus generating an alarm and an output like those from 
gas  reaction.(However,  during  the  circuit  test,  an  output  of  4-20mA  will 
not be made). Gas alarm or circuit test can be return to the start with the 
return switch. (Individual Return) 

Содержание SI-100IA

Страница 1: ...I 100IM MAIN UNIT SI 100IA ALARM DISPLAY UNIT SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM SI 1 0 0 IA SI 1 0 0 IC U...

Страница 2: ...and Description 4 Product s Dimension 6 5 Internal Configuration 3 channel basis 7 6 Terminal Configuration 8 7 Product Instruction for Use 9 SI 100IM Main Alarm Unit SI 100IA Alarm Display Unit 8 Des...

Страница 3: ...chased a route that SENKO does not recognize a product with malfunction cannot be repaired or replaced free of charge when mechanical damages or deformations happen from improper use of the product by...

Страница 4: ...nnel display of a corresponding Alarm Unit on the Main Alarm Unit through the transmitted data so that a user at a glance can notice which alarm unit has given an alarm signal The three Alarm outputs...

Страница 5: ...4Channel While the 24V DC power is introduced for battery charge and discharge and for the power of the Alarm Unit this unit can make an alarm generating unit display by communicating with the Alarm U...

Страница 6: ...ale 13 Alarm Output Fault SPDT Relay Dry contact Signal Output ON OFF Alarm 1 SPDT Relay Dry contact Signal Output ON OFF Alarm 2 SPDT Relay Dry contact Signal Output ON OFF Alarm 3 SPDT Relay Dry con...

Страница 7: ...IMENSION SI 1 0 0 IA SI 1 0 0 IM 3 3 1 2 1 2 V PPM LEL 130 40 110 130 40 SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM...

Страница 8: ...r Switch 8 Built in BATTERY 9 SMPS 24V DC Power Supply 3CH 1 2A 6CH 2 2A 10CH 3 2A 12CH 4 5A 10 FRONT DOOR LINE LOAD ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND F...

Страница 9: ...OUT 4 20mA GND FAULT ALARM 3 ALARM 2 ALARM 1 ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V GAS DETECTOR MAIN UNIT SI 100IM ALARM UNIT SI 100IA 24V 4 20mA GND 3Wire 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND...

Страница 10: ...Unit SI 100IA Alarm Display Unit When the power is turned on the device will display the product software version 1 00 A for 1 sec and an ID of the Unit from 01 to 12 seconds for 4 seconds Then after...

Страница 11: ...efault 15 AL 2 Secondary Alarm Setting Value default 50 AL 3 Tertiary Alarm Setting Value default 70 Span Concentration of Calibration Gas default 25 N AL The number of calibration depending on the ca...

Страница 12: ...rm the device will display the voltage in process of charging and tell you about a state of charging spare power or a state of fully charged Return Switch Once you solve the problem with the gas detec...

Страница 13: ...ration bar graph will arise just as shown in the figures As a concentration rises as shown in the figures the primary secondary and tertiary alarm lamp will be turned on according to an alarm value th...

Страница 14: ...ill be changed Gas Calibration After adjusting the calibration gas concentration SCAL will be displayed If you press the Switch at this status a current gas value will be displayed Zero will be displa...

Страница 15: ...at once Secondary Alarm Value Change default 50 LEL Press the setting switch while AL 2 is shown a default number will be displayed If you need a change while a number is marked change the number by p...

Страница 16: ...ration Range LOW RANGE default 0 Press the Setting Switch when LRNG is displayed and a default value will be displayed Press the UP and DOWN Switch while a figure is being displayed You can change its...

Страница 17: ...when an alarm concentration level is reached Change in 12V Voltage Output default 321 17Press the Setting Switch when 12VO is displayed and a default value will be displayed Press the UP and DOWN Swit...

Страница 18: ...rmal range the alarm and the output will be still stored Even If the device is interlocked with other equipment and thus alarm is repeatedly on and off depending on a concentration a value can changed...