1-2 

Change of an Internal Setting Value 

 

Press  the  setting  and  the  reset  switch  at  the  same  time  for  one  second,  and  the 
device will enter into the mode. (At the setting change entry mode, the power lamp 
will be blinking). 

Primary Alarm Value Change (default 15% LEL) 

Press  the  setting  switch  while  AL-1  is  shown,  a  default  number  will  be 
displayed.  If  you  need  a  change  while  a  number  is  marked,  change  the 
number by  pressing  UP and DOWN Switch. If you press the Setting Switch 
for a second, 

ΞSET 

will be displayed flashing, and the setting will be complete. 

*.  If  you  change  the  number  and  press  the  setting  Switch  for  a  second,  the  mode  will  be 
exited  while  the  following  modification  item  is  not  displayed  (Re-entry  of  setting  mode  is 

required). In order to change all settings without re-entering the setting mode, 
you need to  press the  setting Switch while the  numbers are  already changed. 
Then  AL-1  will  be  displayed  and  all  the  new  settings  will  be  stored  in  the 

internal memory. If you press the circuit test switch > while AL-1 is being displayed, AL-2 will 
be shown; you can change a secondary alarm value or change AL-2 with AL-3. After all the 
settings are finished, click the setting for one second at the final step. If the 

ΞSET 

is blinking, 

all the setting values will be modified at once. 

Secondary Alarm Value Change (default 50% LEL) 

Press  the  setting  switch  while  AL-2  is  shown,  a  default  number  will  be 

displayed.  If  you  need  a  change  while  a  number  is  marked,  change  the 
number by pressing UP and DOWN Switch. If you press the Setting Switch 
for a second, it will be saved and move to the next step.   

Tertiary Alarm Value Change (default 70% LEL) 

Press  the  setting  switch  while  AL-3  is  shown,  a  default  number  will  be 

displayed.  If  you  need  a  change  while  a  number  is  marked,  change  the 
number by pressing UP and DOWN Switch. If you press the Setting Switch 
for a second, it will be saved and move to the next step.   

Changing a Gas Type (default LNG) 

When pressing the Setting Switch while styp is displayed, 

LNG will be 

displayed. If you press the Circuit Test Switch in order to change it into a 
different gas type, you can change a type in an order of LPG-LIN-O2 net. 

*. LNG - When connected to Receiver for LNG, apply to LNG sensor gas table. 
LPG - When connected to receiver for 

LPG

 gas, apply to 

LPG

 sensor gas table.   

LIN  -  When  connected  to  receiver  other  than 

LPG

  and  LNG,  apply  to  a  sensor  with  linear 

reaction applied. O2-When connected to Oxygen Receiver (all settings are modified to match 
oxygen) RANGE (0 ~ 30%) Primary alarm (19%), Secondary alarm (17%), Tertiary alarm (23%) 

Once you have entry into the setting mode, you press the circuit test switch. Then its corresponding items 
will be changed sequentially. (AL-1, AL-2, AL-3, STYP ............). You can pick one selectively and change 
it. 

LEL

LEL

Содержание SI-100IA

Страница 1: ...I 100IM MAIN UNIT SI 100IA ALARM DISPLAY UNIT SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM SI 1 0 0 IA SI 1 0 0 IC U...

Страница 2: ...and Description 4 Product s Dimension 6 5 Internal Configuration 3 channel basis 7 6 Terminal Configuration 8 7 Product Instruction for Use 9 SI 100IM Main Alarm Unit SI 100IA Alarm Display Unit 8 Des...

Страница 3: ...chased a route that SENKO does not recognize a product with malfunction cannot be repaired or replaced free of charge when mechanical damages or deformations happen from improper use of the product by...

Страница 4: ...nnel display of a corresponding Alarm Unit on the Main Alarm Unit through the transmitted data so that a user at a glance can notice which alarm unit has given an alarm signal The three Alarm outputs...

Страница 5: ...4Channel While the 24V DC power is introduced for battery charge and discharge and for the power of the Alarm Unit this unit can make an alarm generating unit display by communicating with the Alarm U...

Страница 6: ...ale 13 Alarm Output Fault SPDT Relay Dry contact Signal Output ON OFF Alarm 1 SPDT Relay Dry contact Signal Output ON OFF Alarm 2 SPDT Relay Dry contact Signal Output ON OFF Alarm 3 SPDT Relay Dry con...

Страница 7: ...IMENSION SI 1 0 0 IA SI 1 0 0 IM 3 3 1 2 1 2 V PPM LEL 130 40 110 130 40 SI 1 0 0 IM 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SI 1 0 0 IA 3 1 2 PPM LEL V SPARE BLANK Multi G a s Monitor SI 1 0 0 IM...

Страница 8: ...r Switch 8 Built in BATTERY 9 SMPS 24V DC Power Supply 3CH 1 2A 6CH 2 2A 10CH 3 2A 12CH 4 5A 10 FRONT DOOR LINE LOAD ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND F...

Страница 9: ...OUT 4 20mA GND FAULT ALARM 3 ALARM 2 ALARM 1 ALARM 3 ALARM 2 ALARM 1 12V OUT GND 0V 24V GAS DETECTOR MAIN UNIT SI 100IM ALARM UNIT SI 100IA 24V 4 20mA GND 3Wire 24VS SENSOR SIG 0VS 12V OUT 4 20mA GND...

Страница 10: ...Unit SI 100IA Alarm Display Unit When the power is turned on the device will display the product software version 1 00 A for 1 sec and an ID of the Unit from 01 to 12 seconds for 4 seconds Then after...

Страница 11: ...efault 15 AL 2 Secondary Alarm Setting Value default 50 AL 3 Tertiary Alarm Setting Value default 70 Span Concentration of Calibration Gas default 25 N AL The number of calibration depending on the ca...

Страница 12: ...rm the device will display the voltage in process of charging and tell you about a state of charging spare power or a state of fully charged Return Switch Once you solve the problem with the gas detec...

Страница 13: ...ration bar graph will arise just as shown in the figures As a concentration rises as shown in the figures the primary secondary and tertiary alarm lamp will be turned on according to an alarm value th...

Страница 14: ...ill be changed Gas Calibration After adjusting the calibration gas concentration SCAL will be displayed If you press the Switch at this status a current gas value will be displayed Zero will be displa...

Страница 15: ...at once Secondary Alarm Value Change default 50 LEL Press the setting switch while AL 2 is shown a default number will be displayed If you need a change while a number is marked change the number by p...

Страница 16: ...ration Range LOW RANGE default 0 Press the Setting Switch when LRNG is displayed and a default value will be displayed Press the UP and DOWN Switch while a figure is being displayed You can change its...

Страница 17: ...when an alarm concentration level is reached Change in 12V Voltage Output default 321 17Press the Setting Switch when 12VO is displayed and a default value will be displayed Press the UP and DOWN Swit...

Страница 18: ...rmal range the alarm and the output will be still stored Even If the device is interlocked with other equipment and thus alarm is repeatedly on and off depending on a concentration a value can changed...

Отзывы: